Inspections for the day of: Thursday, May 9, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01872 Final5/8/20195/9/20195/9/2019 3:50:25 PMPFAIL
Andrew ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
-need to see all duct work completely sealed
- one duct seam is not joined together properly
MEC19-01852 Final5/6/20195/9/20195/9/2019 3:11:28 PMPFAIL
Heat pump and coil change out Phone #: ###-#### Inspection requested via web by Brian Preece
- HP needs 25 amp fuses installed
MEC19-01829 Pressure Test5/8/20195/9/20195/9/2019 3:03:41 PMPPASS
Please call Brian C at ###-#### when in route or Gill at ###-####. Phone #: ###-#### Inspection requested via web by Sabrina DeHority
- 20lb gas pressure test ok
MEC19-01828 Final5/7/20195/9/20195/9/2019 2:17:17 PMPPASS
Bill ; Rita Landriani ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-00994 Final5/7/20195/9/20195/9/2019 1:50:16 PMPPASS
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire
- final ok
MEC19-01920 Pressure Test5/9/20195/9/20195/9/2019 1:30:52 PMPPASS
Rick- this is a rental and tenant will be home all day Phone #: ###-####
- 20lb gas pressure test ok
MEC18-04616 Mec-Aging Inspection5/9/20195/9/20195/9/2019 11:12:28 AM FAIL
This permit has not been active since doing a pressure test on new gas line. If furnace and work is finished schedule an inspection with the homeowner. Permit is over 180 days old and will be expired if not active by the next aging inspection. Permit will have to be re issued and fees pay again to have inspection after expiration
MEC18-04703 Final5/8/20195/9/20195/9/2019 11:06:02 AMAFAIL
Terek Phone #: ###-####
- combustion air for tankless water heater needs to be piped out with PVC talked with Ernie about what needs to be done
MEC18-04703 Conference5/9/20195/9/20195/9/2019 11:04:42 AMAPASS
Terek Phone #: ###-####
- duct blast pass west unit only
MIS19-00122 MEC-Conference5/9/20195/9/20195/9/2019 10:04:33 AMAFAIL
need to pull mechanical permit for dryer vent/ exhaust fans/ and the relocation of the gas line
MEC19-01930 Final5/8/20195/9/20195/9/2019 9:50:12 AMAPASS
Please call 30 mins. before going. Phone #: ###-#### Inspection requested via web by Rene Neumeyer
- fireplace final ok
MEC19-01930 Pressure Test5/9/20195/9/20195/9/2019 9:49:54 AMAPASS
Please call 30 mins. before going. Phone #: ###-#### Inspection requested via web by Rene Neumeyer
- 20lb gas pressure test ok
MEC17-05415 Mec-Aging Inspection5/9/20195/9/20195/9/2019 9:09:01 AM PASS
permit expired
MEC17-05415 DOC - Permit Expired5/9/20195/9/20195/9/2019 9:08:45 AMAPASS
MEC19-01862 Pressure Test5/8/20195/9/20195/9/2019 9:06:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 20lb gas pressure test ok
- tagged meter location
MEC19-01862 Rough-in5/8/20195/9/20195/9/2019 9:05:44 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- fresh air intake needs to be installed at return plenum near furnace
- line set insulation in crawl needs fixed
MEC19-01864 Pressure Test5/8/20195/9/20195/9/2019 9:04:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart
- 20lb gas pressure test ok
- tagged meter location
MEC19-01864 Rough-in5/8/20195/9/20195/9/2019 9:04:31 AMAFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart
- need stamped Man J. onsite
- fresh air intake needs to be installed at return plenum near furnace
- dryer vent penetration at floor needs sealed
- line set insulation in kitcken wall needs fixed at top plate