FIR18-00815
| INSP-Final Inspection | 5/9/2019 | 5/9/2019 | 5/9/2019 12:00:00 AM | P | FAIL |
|
|
Checked prints with cut sheets. Tested notification, gym circuit worked. On testing duct detectors, none of the fans shut down. Wires were disconnected on the fire alarm interface in the roof top unit. Protex is to fix the issue with shutdown and verify all units shut down. Next test will need to test all 5 duct detectors for shurdown.
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
|