FIR04-00179
| INSP-Sprinkler Rough-in/Hydro | 5/27/2004 | 6/1/2004 | 6/1/2004 12:00:00 AM | A | FAIL |
|
|
Contact: Charles; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Heads overspaced in kitchen; tape on heads; need cages on heads in several areas; head in freezer appears to be leaking; need resubmittals for thatch canopies that have heads under them and for changes to under stair piping 6/1/2004 11:30:17 AM
|
BLD04-00666
| FIRE-Conference | 5/28/2004 | 6/1/2004 | 6/1/2004 12:00:00 AM | A | PART |
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Annette Moore Met with GC: fire sprinklers overpsaced in some office and within 6 ft of each other in hallway; sprinkler system overdue on annual inspection; relocate exit sign in office to above hallway opening to lobby; extinguishers needed; fire alarm system monitors sprinklers and there are smoke detectors throughout the building with notification in some areas but not in permitted area restrooms; smoke detector is above panel located in east lobby but cabinet was locked - couldn't verify batteries 6/1/2004 10:41:05 AM
|
BLD04-00728
| FIRE-Final Inspection | 6/1/2004 | 6/1/2004 | 6/1/2004 12:00:00 AM | A | PASS |
|
|
|
FIR04-00287
| INSP-Final Inspection | 6/1/2004 | 6/1/2004 | 6/1/2004 12:00:00 AM | A | PASS |
|
|
|
FIR04-00293
| INSP-Final Inspection | 6/1/2004 | 6/1/2004 | 6/1/2004 12:00:00 AM | P | NR |
|
|
Darren; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes will reschedule 6/1/2004 3:58:29 PM
|
FIR03-00214
| INSP-Final Inspection | 5/28/2004 | 6/1/2004 | 6/1/2004 12:00:00 AM | P | FAIL |
|
|
bob erland; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Need NFPA 25 6/1/2004 3:59:30 PM
|