Inspections for the day of: Wednesday, June 1, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00730 INSP-Final Inspection5/31/20056/1/20056/1/2005 3:47:08 PM PART
Final pending map at panel, signage at door to FACP, signal verification, and removal of temp. covers on detection devices.
FIR05-00061 INSP-Final Inspection6/1/20056/1/20056/1/2005 1:48:26 PMPPART
Fire alarm passed inspection on the 12th floor only.
FIR05-00256 INSP-Sprinkler Rough-in/Hydro6/1/20056/1/20056/1/2005 12:58:03 PMPPART
Fire sprinkler rough in OK for cover.
BLD04-02942 FIRE-Final Inspection6/1/20056/1/20056/1/2005 11:23:25 AMPFAIL
Door at east exit to corridor must have code approved hardware. All remaining life safety issues are satisfactory.
BLD05-00053 FIRE-Final Inspection5/31/20056/1/20056/1/2005 10:38:26 AMAPASS
Fire life safety finaled.
FIR05-00236 INSP-Conference5/31/20056/1/20056/1/2005 9:36:44 AMADONE
Done. Walk through with Phil Doble and Dave Hannah area C. Discussed project phasing and inspection schedule.
FIR05-00187 INSP-Final Inspection6/1/20056/1/20056/1/2005 12:00:00 AMAPASS
Fire sprinkler finaled.
FIR04-00811 INSP-Final Inspection6/1/20056/1/20056/1/2005 12:00:00 AMAPASS
Fire sprinkler finaled.
FIR05-00146 INSP-Final Inspection6/1/20056/1/20056/1/2005 12:00:00 AMPPASS
Fire sprinkler finaled.
FIR05-00010 INSP-Final Inspection6/1/20056/1/20056/1/2005 12:00:00 AMPPASS
Fire sprinkler finaled for 12th floor only.
FIR04-00593 INSP-Final Inspection6/1/20056/1/20056/1/2005 12:00:00 AMPPART
Alarms and riser functionality tested. Final pending head wrench, tags, foreward flow test, bell sign, canopies, drain map, and backflow certification.
BLD04-02942 FIRE-Final Inspection6/1/20056/1/20056/1/2005 12:00:00 AMPPASS
Fire life safety finaled.