Inspections for the day of: Wednesday, June 1, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01287 FIRE-Final Inspection6/1/20056/1/20056/2/2005 9:50:01 AMPPART
A temporary occupancy was given until the manual releases for the smoke vents have been installed, provide "max. height" signage as discussed, reduce outside storage to 12' max
BLD00-03017 FIRE-Final Inspection6/1/20056/1/20056/2/2005 9:16:17 AMPFAIL
Shell ok to final when grading permit is finaled
BLD05-00264 FIRE-Final Inspection6/1/20056/1/20056/2/2005 9:15:04 AMPFAIL
final shell and grading permis, remove thumbturns and provide approved hardware on the south exit door and mechanical room doors, provide inspection for the fire extinguisher and lower to 48"
FIR05-00217 INSP-Sprinkler Rough-in/Hydro6/1/20056/1/20056/1/2005 1:19:34 PMPPART
The dry system rough-in is ok except for one head needs to be added in the south east room. Contractor needs to get with Bill Alexander to see if a resubmittal will be required for this head and the three other dry uprights added at each of the entrances.
BLD05-00310 FIRE-Final Inspection6/1/20056/1/20056/1/2005 1:05:41 PMPFAIL
walt; Phone #: ###-####
Need three fire extinguishers, two for the new shop and one for the existing building. New addition is empty. I can't verify storage or flammables.
FIR05-00149 INSP-Final Inspection5/31/20056/1/20055/31/2005 4:19:36 PMPFAIL
sprinkler piping in bedroom is now ok to cover