Inspections for the day of: Thursday, June 1, 2006.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00736 ELE-Aging Inspection6/1/20066/1/20066/1/2006 4:17:02 PM DONE
ELE06-00736 Final6/1/20066/1/20066/1/2006 4:16:49 PMPPASS
ok
ELE06-01956 Electrical Rough-In6/1/20066/1/20066/1/2006 3:41:12 PMPCANC
vivian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
ELE06-01956 Rough-In Permanent Service6/1/20066/1/20066/1/2006 3:40:59 PMPPASS
vivian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. made r/i p/s u/g new ok
ELE05-04629 Final6/1/20066/1/20066/1/2006 3:09:42 PMPFAIL
larry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called 410.8 install closet fixture , provide required clearence,314.16 box fill end of pen. counter, 406.4(A B D) all areas, 408.4 panel schedule shall note location and specific purpose of circuits, does catv cabinet in attic access in closet require power? if so wire it
ELE06-02003 Electrical Rough-In6/1/20066/1/20066/1/2006 2:18:48 PMPPART
TYLER CALL PRIOR TO COMMING OUT CAN WE MAKE THIS YOUR LAST STOP TODAY; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
u/g ok this is behind 8109 w franklin east end
ELE06-01989 Permanent Service5/31/20066/1/20066/1/2006 1:41:02 PMPPASS
inspection on 100 amp service upgrade will be ready around 1:00 any questions call Tate @###-#### Internet Inspection Request from: Andy Rose p/s u/g rec. ok
ELE06-01989 Final6/1/20066/1/20066/1/2006 1:40:40 PMPCANC
inspection on 100 amp service upgrade will be ready around 1:00 any questions call Tate @###-#### Internet Inspection Request from: Andy Rose ok - cancell per jack frank and reopened 6/02/06
ELE06-01704 Permanent Service6/1/20066/1/20066/1/2006 1:01:17 PMPPASS
Roger; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
p/s o/h rec. ok
ELE06-01704 Final6/1/20066/1/20066/1/2006 1:00:50 PMPPASS
Roger; Phone #: ###-#### Internet Inspection ok
upt
ELE06-01986 Electrical Rough-In6/1/20066/1/20066/1/2006 12:11:08 PMPPART
tom - pull bond; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
pool bond only still needs equip. grid and bonding of all metal on house called
ELE06-01956 Rough-In Permanent Service5/31/20066/1/20066/1/2006 11:38:17 AMAFAIL
Scheduled by a contractor via Hello! on 5/31/2006 at 12:53:46 PM. Contact: ###-####. nail plates and 11/4" called
ELE06-00422 Electrical Rough-In5/31/20066/1/20066/1/2006 10:14:11 AMAPART
any questions please call Steve Nuxoll; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ist floor east end lobby soffit ok
ELE06-01986 Conference5/31/20066/1/20066/1/2006 9:53:23 AMACANC
Tom, check grounding on pool; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called they need r/i not conference
ELE06-01976 Permanent Service5/31/20066/1/20066/1/2006 9:33:22 AMAFAIL
please call if you have ?'s ; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corr called 110.3(A)6 &12(C) replace panel bus damaged from arcing 110.12(A) seal KOs panel, 250.24(A)(1) treminate all bonds AND GEC to neutral bus 110.(A&B) install manufactures bond screw, 334.80 if over 2 cables per hole derate, 300.4(A)(1&2) nail plates note if attic access is in garage protect cables within 6ft
ELE05-03853 Final6/1/20066/1/20066/1/2006 8:36:32 AMPCANC
BILL; Phone #: ###-#### Internet Inspection Request from: Bob Glenn Inspection cancelled from web by: Bob Glenn
ELE06-01798 Conference6/1/20066/1/20066/1/2006 8:26:20 AMACANC
Scheduled by a contractor via Hello! on 6/1/2006 at 6:02:29 AM. Contact: ###-####. see added final request
ELE06-01798 Final6/1/20066/1/20066/1/2006 8:25:51 AMAPASS
Scheduled by a contractor via Hello! on 6/1/2006 at 6:02:29 AM. Contact: ###-####. vision center ok for ceiling cover corrections made and temp occupancy ok
ELE06-01704 Final6/1/20066/1/20066/1/2006 12:00:00 AMPCANC
roger; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles canceld per contractor