BLD06-00213
| FIRE-Final Inspection | 5/31/2006 | 6/1/2006 | 6/2/2006 7:48:26 AM | P | FAIL |
|
|
The project related fire sprinkler permit must be requested for final inspection and approved prior to life safety final.
|
FIR05-00738
| INSP-Supply line flush | 5/31/2006 | 6/1/2006 | 6/2/2006 7:44:24 AM | P | PART |
|
|
UG supply line flush performed satisfactory.
|
BLD06-01348
| FIRE-Conference | 5/31/2006 | 6/1/2006 | 6/2/2006 7:43:19 AM | A | DONE |
|
|
On site confrence to discuss the need for a fire alarm permit if any modifications or alterations are made to the existing fire alarm system during the course of building remodel.
|
FIR06-00288
| INSP-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 1:26:58 PM | A | PASS |
|
|
Final fire sprinkler inspection passed, permit finaled.
|
BLD06-00320
| FIRE-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 1:25:44 PM | A | PASS |
|
|
Correction notice items are complete, fire life safety finaled.
|
BLD06-00322
| FIRE-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 1:24:45 PM | A | PASS |
|
|
Items on correction notice have been completed, fire life safety inspection passed.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 5/31/2006 | 6/1/2006 | 6/1/2006 12:40:28 PM | A | FAIL |
|
|
Overhead rough-in inspection for cover at the 9th floor failed due to nearly all the piping having been concealed above the ceiling by sheetrock hard lids previous to inspection. No inspection could be performed, notified general contractor of the need to expose the pipe for viewing prior to next inspection request. See note #255 on fire code plan review.
|
BLD06-00024
| FIRE-Final Inspection | 6/1/2006 | 6/1/2006 | 6/1/2006 12:33:58 PM | P | PASS |
|
|
Life safety inspection is satisfactory.
|
BLD06-00825
| FIRE-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 12:32:27 PM | A | FAIL |
|
|
Need to provide emergency lighting as noted on plan.
|
FIR06-00323
| INSP-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 12:30:46 PM | A | PASS |
|
|
Fire sprinkler passed final inspection.
|
FIR06-00277
| INSP-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|