Inspections for the day of: Thursday, June 1, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00616 Final5/31/20066/1/20066/1/2006 10:54:15 PMPFAIL
chad; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
1. 314.28A1--- Need to properly size j-box for feeder pull.
2. 300.11A--- Raceways shall have thier own support wires and be identified.
3. 110.26--- working clearences for the sub-panel.
ELE06-01612 Electrical Rough-In6/1/20066/1/20066/1/2006 4:34:29 PMPPASS
Underground; Phone #: ###-#### Internet Inspection Request from: Jim Williams
slab on grade underground ok to cover
ELE05-03525 Final6/1/20066/1/20066/1/2006 4:29:36 PMPPASS
BILL; Phone #: ###-#### Internet Inspection Request from: Bob Glenn
ELE06-01691 Electrical Rough-In5/31/20066/1/20066/1/2006 2:41:31 PMPPART
UNDERGROUND SERVICE INSPECTION ALT PHONE ###-####; Phone #: ###-#### Internet Inspection Request from: Cathy Felin
1. All underground ok, except east side of yard.
ELE06-01548 Electrical Rough-In6/1/20066/1/20066/1/2006 2:15:46 PMPCANC
robere; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ELE06-01548 Conference6/1/20066/1/20066/1/2006 2:15:33 PMPDONE
robere; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
talked about new service, 1 1/4" protection, nail plates, make up, and a butt load of other things.
ELE06-01837 Final6/1/20066/1/20066/1/2006 1:05:51 PMPPASS
this is for the service only, we were unable to get co-operation from the owner for the interior.
ELE06-01837 Permanent Service6/1/20066/1/20066/1/2006 1:04:26 PMPPASS
p/s o/h reconnect ok
ELE05-04614 Final5/31/20066/1/20066/1/2006 12:39:51 PMAFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
1. 410.8-- mstrbdrm closet fixture
ELE06-00278 Final5/31/20066/1/20066/1/2006 11:04:30 AMAPASS
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
ELE06-00279 Final5/31/20066/1/20066/1/2006 10:55:31 AMAPASS
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
ELE06-01999 Permanent Service5/31/20066/1/20066/1/2006 10:08:25 AMAPASS
lee - ###-#### (Note: office ####-####)
p/s u/g reconnect ok
ELE06-01971 Temporary Service5/31/20066/1/20066/1/2006 9:42:34 AMAPASS
###-####
t/s u/g n ok
ELE06-02000 Temporary Service5/31/20066/1/20066/1/2006 9:08:54 AMAPASS
Verna; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
t/s u/g n ok