FIR06-00950
| FIR-Aging Inspection | 6/1/2007 | 6/1/2007 | 6/7/2007 1:52:16 PM | | DEFR |
|
|
|
FIR07-00303
| INSP-Sprinkler Rough-in | 5/30/2007 | 6/1/2007 | 6/1/2007 3:11:58 PM | A | PART |
|
|
Overhead fire sprinkers are okay for cover at the drop ceilings as noted on plans.
|
FIR07-00298
| INSP-Sprinkler Rough-in | 5/30/2007 | 6/1/2007 | 6/1/2007 3:11:08 PM | A | PART |
|
|
TI fire sprinklers are okay for cover.
|
FIR07-00453
| INSP-Final Inspection | 5/31/2007 | 6/1/2007 | 6/1/2007 3:10:19 PM | A | FAIL |
|
|
Spacing exceeds design per calculations at several locations, one closet on the first floor will require a drop ceiling or extended walls to the deck for upright protection, no access to the front elevator lobby and restrooms due to floor finishes, installation is not approved for cover at this time.
|
BLD04-01820
| FIRE-Final Inspection | 6/1/2007 | 6/1/2007 | 6/1/2007 1:59:01 PM | P | PASS |
|
|
Shell life safety passed.
|
FIR07-00353
| INSP-Sprinkler Rough-in | 5/30/2007 | 6/1/2007 | 6/1/2007 1:58:18 PM | A | PART |
|
|
OH fire sprinklers are approved for ceiling cover.
|
FIR07-00302
| INSP-Sprinkler Rough-in | 5/30/2007 | 6/1/2007 | 6/1/2007 1:57:35 PM | A | PART |
|
|
FP is good for cover at the hard lid ceilings.
|
BLD06-01681
| FIRE-Final Inspection | 5/30/2007 | 6/1/2007 | 6/1/2007 1:56:35 PM | A | FAIL |
|
|
Need to post building address numbers, mount fire extinguisher as discussed, provide approved hardware at the two pool enclosure gates, manual thumbturns at the two restroom doors are not allowed, also need to provide approved plans and inspection record card at next visit.
|
BLD07-00976
| FIRE-Final Inspection | 5/30/2007 | 6/1/2007 | 6/1/2007 12:21:28 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR07-00361
| INSP-Final Inspection | 5/30/2007 | 6/1/2007 | 6/1/2007 12:20:48 PM | A | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
FIR07-00383
| INSP-Final Inspection | 5/30/2007 | 6/1/2007 | 6/1/2007 12:20:01 PM | A | PASS |
|
|
Fire sprinkler work passed inspection, permit finaled.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 5/31/2007 | 6/1/2007 | 6/1/2007 12:19:00 PM | A | PART |
|
|
OH fire sprinkler install is okay for cover at the drop ceilings for a portion of the NW quad 1st floor remodel as red lined and initialed on plans.
|
BLD06-02431
| FIRE-Final Inspection | 5/31/2007 | 6/1/2007 | 6/1/2007 12:16:32 PM | A | PASS |
|
|
Life safety inspection passed, fire extinguisher installed while on site, doors at some locations are not installed-verified hardware type is approved, provided signage at the main entry/exit to be attatched when finishes are complete.
|
FIR07-00313
| INSP-Final Inspection | 5/29/2007 | 6/1/2007 | 5/31/2007 4:05:23 PM | P | CANC |
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Victoria Beall
|