FIR06-00958
| INSP-Sprinkler Rough-in/Hydro | 5/29/2007 | 6/1/2007 | 6/4/2007 3:14:46 PM | A | PART |
|
|
Attic and third floor piping rough in is passed but a tenting inspection is still needed per brian and the hydro test failed.
|
BLD06-03431
| FIRE-Final Inspection | 6/1/2007 | 6/1/2007 | 6/1/2007 2:53:01 PM | P | PASS |
|
|
life safety passed
|
FIR07-00006
| INSP-Final Inspection | 5/29/2007 | 6/1/2007 | 6/1/2007 2:51:09 PM | P | PASS |
|
|
permit finaled
|
BLD07-00573
| FIRE-Final Inspection | 5/31/2007 | 6/1/2007 | 6/1/2007 2:50:16 PM | A | FAIL |
|
|
Need exit discharge lighting and tags on the fire extinguishers
|
BLD07-01201
| FIRE-Final Inspection | 5/31/2007 | 6/1/2007 | 6/1/2007 1:51:18 PM | A | FAIL |
|
|
The new insulation backing is laying on the upright sprinklers deflectors in many location. Code requires 1" clearance.
|
BLD07-00479
| FIRE-Final Inspection | 6/1/2007 | 6/1/2007 | 6/1/2007 12:03:14 PM | A | PASS |
|
|
life safety passed
|
FIR06-00485
| INSP-Sprinkler Rough-in/Hydro | 5/31/2007 | 6/1/2007 | 6/1/2007 8:57:24 AM | A | PART |
|
|
See the city approved plans for locations where sprinklers need to be added and insulation reattached to the roof deck. The sidewall sprinklers at the main entrance are too far from the deck. As-builts need to resubmitted showing the added line in the dining/remote area.
|