Inspections for the day of: Monday, June 1, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-03235 Final5/29/20096/1/20096/1/2009 4:22:42 PMPPART
Jared-Please call for access Phone #: ###-#### done except for kitchen- tlie man working in there, will see when receptacles installed, needs to close box in attic and provide globes for lights in closet, no esc this project
ESC09-00147 General Inspection6/1/20096/1/20096/1/2009 4:07:35 PMPPASS
looked ok
ELE08-02050 Final6/1/20096/1/20096/1/2009 3:59:31 PMPFAIL
doug Phone #: ###-#### met owner, left correction notice, NEC 422.31(B)shall provide locking device for water heater to disconnect from circuit and tighten fitting, 422.16(B) length of disposal shall not exceed 36", 210.52(B)(2) there shall be no other outlets on the 2 or more small appliance branch circuits, 406.8(B) rear outside receptacle shall be listed weather resistant and be provided with weatherproof enclosure (in-use cover), no esc this project
ELE09-00851 Electrical Rough-In5/29/20096/1/20096/1/2009 3:15:00 PMPPASS
Scheduled by a contractor via Hello! on 5/29/2009 at 2:36:34 PM. Contact: ###-####. ok to cover walls, and ceiling, no esc this project
ELE07-02797 Final6/1/20096/1/20096/1/2009 2:15:50 PMPPASS
paul Phone #: ###-#### ok to final, no esc this project
ELE09-00936 Permanent Service6/1/20096/1/20096/1/2009 1:23:45 PMPCANC
Dave Phone #: ###-#### talked with contractor, told to check out and bring up to code, call for inspection and provide access
ELE09-00836 Permanent Service6/1/20096/1/20096/1/2009 12:36:16 PMPPASS
If you have any questions, please call Clay. Someone will be there. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan ok to cover concrete encased electrode, p/s u/g rec ok
ESC09-00229 General Inspection6/1/20096/1/20096/1/2009 9:50:47 AMAPASS
looked ok, saw sign and container
ELE09-00931 Rough-In Permanent Service5/29/20096/1/20096/1/2009 9:22:49 AMAPASS
Tom Phone #: ###-#### ric ok, p/s u/g n ok
ELE09-00905 Electrical Rough-In5/30/20096/1/20096/1/2009 8:31:10 AMAPASS
1st thing AM if possiable Phone #: ###-#### Internet Inspection Request from: David Seilheimer ric ok, no esc this project