Inspections for the day of: Tuesday, June 1, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00781 FIR-Aging Inspection6/1/20106/1/20106/3/2010 11:03:03 AM PASS
permit finaled
FIR09-00728 INSP-Final Inspection6/1/20106/1/20106/2/2010 7:24:42 AMPCANC
Cancelled due to time constraints. Rescheduled for tomorrow.
BLD10-00608 FIRE-Conference5/28/20106/1/20106/1/2010 4:23:09 PMACANC
Had to cancel due to time constraints. Rescheduled for tomorrow.
BLD09-00980 FIRE-Final Inspection5/26/20106/1/20106/1/2010 3:32:30 PMAFAIL
See correction notice for deficiencies.
FIR09-00708 INSP-Sprinkler Rough-in6/1/20106/1/20106/1/2010 3:28:37 PMPPASS
Forward flush passed.
BLD09-00557 FIRE-Final Inspection5/28/20106/1/20106/1/2010 3:21:13 PMAFAIL
Provide test report for the kitchen hood and the fire sprinkler permit needs to be finaled. Alarm permit finaled today. Occupant load signs for the assembly areas are temporary until the permanent ones are installed.
BLD10-00797 FIRE-Final Inspection6/1/20106/1/20106/1/2010 3:08:21 PMPFAIL
Provide single action hardware on the north store front door as discussed. I measured the travel distance to the existing main exit and it exceeded 75' so this north door is required and can not be deleted. The rear exit door in the storage area needs the thumbturn lock removed and single action hardware installed.
FIR09-00711 INSP-Final Inspection5/28/20106/1/20106/1/2010 2:38:30 PMPPASS
Permit finaled. Remaining deficiencies corrected.
FIR06-00710 INSP-Final Inspection5/27/20106/1/20106/1/2010 1:26:40 PMAPASS
Jeff and I met at the project and went over the drawings. It appears the 8' isles referenced was a typo since in the design curve "C" was used which covers multiple racks and 4' isles. Permit finaled.
BLD07-02624 FIRE-Final Inspection6/1/20106/1/20106/1/2010 11:49:30 AMAPASS
life safety passed
BLD06-02047 FIRE-Final Inspection6/1/20106/1/20106/1/2010 11:48:34 AMAPASS
life safety passed