ESC11-00155
| General Inspection | 6/1/2011 | 6/1/2011 | 6/2/2011 2:30:59 PM | | DONE |
|
|
looked ok, just dumped load of gravel in street, had bucket tractor on site where dumped
|
ELE11-00286
| Electrical Rough-In | 5/31/2011 | 6/1/2011 | 6/1/2011 3:01:45 PM | P | PASS |
|
|
devon Phone #: ###-#### corrections as noted done, called, left message, shall add receptacle front and rear dwelling by final, also shall close openings in panel with correct closure plates
|
ELE11-01118
| Temporary Service | 6/1/2011 | 6/1/2011 | 6/1/2011 2:59:20 PM | P | FAIL |
|
|
George Phone #: ###-#### called, left correction notice, NEC 250.53(G) upper end ground rod shall be flush with or below ground level, 312.5 all conductors entering enclosure shall have abrasion protection, 406.8(B) 125v receptacle shall be listed weather-resistant, BCC shall post job id sticker
|
ELE11-01062
| Electrical Rough-In | 6/1/2011 | 6/1/2011 | 6/1/2011 2:54:59 PM | P | PART |
|
|
pat Phone #: ###-#### ri ok except where tailed romex not boxed upstairs and bathrooms
|
ELE11-00716
| Electrical Rough-In | 5/31/2011 | 6/1/2011 | 6/1/2011 1:30:16 PM | P | PASS |
|
|
victoria - please call 1/2 hr prior Phone #: ###-#### ok over main floor and upstairs
|
ELE11-00875
| Electrical Rough-In | 6/1/2011 | 6/1/2011 | 6/1/2011 12:39:29 PM | P | PART |
|
|
Geoff Hannaford is contact on this job. ###-#### Phone #: ###-#### >> Inspection requested via web by Debby Ellis walls ok cover, will come back for lighting and boxes, will change room count to 13 rooms
|
ELE10-02478
| ELE-Aging Inspection | 6/1/2011 | 6/1/2011 | 6/1/2011 10:16:42 AM | | DONE |
|
|
waiting for call for access per card and call
|
ELE11-00567
| Final | 6/1/2011 | 6/1/2011 | 6/1/2011 10:14:47 AM | A | FAIL |
|
|
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn called, left correction notice, BCC all fixtures shall be installed, NEC 110.3(B) listed equipment shall be installed per manufacturers instructions
|
ELE11-01098
| Electrical Rough-In | 5/31/2011 | 6/1/2011 | 6/1/2011 9:25:54 AM | A | PASS |
|
|
key above door if locked corrections made Phone #: ###-#### >> Inspection requested via web by Don Lustig corrections made, ri ceiling and walls ok cover
|
ELE11-01098
| Permanent Service | 5/31/2011 | 6/1/2011 | 6/1/2011 8:57:02 AM | A | PASS |
|
|
key above door if locked corrections made Phone #: ###-#### >> Inspection requested via web by Don Lustig p/s exst meter pak n ok
|
ELE11-01050
| Electrical Rough-In | 5/31/2011 | 6/1/2011 | 6/1/2011 8:18:51 AM | A | PASS |
|
|
Mike is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates ri ok
|