Inspections for the day of: Wednesday, June 1, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC11-00155 General Inspection6/1/20116/1/20116/2/2011 2:30:59 PM DONE
looked ok, just dumped load of gravel in street, had bucket tractor on site where dumped
ELE11-00286 Electrical Rough-In5/31/20116/1/20116/1/2011 3:01:45 PMPPASS
devon Phone #: ###-#### corrections as noted done, called, left message, shall add receptacle front and rear dwelling by final, also shall close openings in panel with correct closure plates
ELE11-01118 Temporary Service6/1/20116/1/20116/1/2011 2:59:20 PMPFAIL
George Phone #: ###-#### called, left correction notice, NEC 250.53(G) upper end ground rod shall be flush with or below ground level, 312.5 all conductors entering enclosure shall have abrasion protection, 406.8(B) 125v receptacle shall be listed weather-resistant, BCC shall post job id sticker
ELE11-01062 Electrical Rough-In6/1/20116/1/20116/1/2011 2:54:59 PMPPART
pat Phone #: ###-#### ri ok except where tailed romex not boxed upstairs and bathrooms
ELE11-00716 Electrical Rough-In5/31/20116/1/20116/1/2011 1:30:16 PMPPASS
victoria - please call 1/2 hr prior Phone #: ###-#### ok over main floor and upstairs
ELE11-00875 Electrical Rough-In6/1/20116/1/20116/1/2011 12:39:29 PMPPART
Geoff Hannaford is contact on this job. ###-#### Phone #: ###-#### >> Inspection requested via web by Debby Ellis walls ok cover, will come back for lighting and boxes, will change room count to 13 rooms
ELE10-02478 ELE-Aging Inspection6/1/20116/1/20116/1/2011 10:16:42 AM DONE
waiting for call for access per card and call
ELE11-00567 Final6/1/20116/1/20116/1/2011 10:14:47 AMAFAIL
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn called, left correction notice, BCC all fixtures shall be installed, NEC 110.3(B) listed equipment shall be installed per manufacturers instructions
ELE11-01098 Electrical Rough-In5/31/20116/1/20116/1/2011 9:25:54 AMAPASS
key above door if locked corrections made Phone #: ###-#### >> Inspection requested via web by Don Lustig corrections made, ri ceiling and walls ok cover
ELE11-01098 Permanent Service5/31/20116/1/20116/1/2011 8:57:02 AMAPASS
key above door if locked corrections made Phone #: ###-#### >> Inspection requested via web by Don Lustig p/s exst meter pak n ok
ELE11-01050 Electrical Rough-In5/31/20116/1/20116/1/2011 8:18:51 AMAPASS
Mike is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates ri ok