ELE11-01976
| ELE-Aging Inspection | 6/1/2016 | 6/1/2016 | 6/3/2016 2:40:05 PM | | CANC |
|
|
|
ELE16-01732
| Electrical Rough-In | 5/31/2016 | 6/1/2016 | 6/2/2016 8:21:13 AM | A | FAIL |
|
|
There should be someone there. If you have any questions, please call Jared at ###-####, thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan 314.23- Boxes shall be secured. 2 boxes in master bed and bath hanging on wire. 314.29- All boxes shall be accessible. Box to left of fireplace appears to have no access when rocked.
|
ELE13-00256
| Final | 5/31/2016 | 6/1/2016 | 6/1/2016 2:42:00 PM | P | FAIL |
|
|
Ryan Phone #: ###-#### 210.8- All receptacles installed in residential garage shall have GFCI protection. 300.4- Where NM cable is ran through bored holes, Holes shall be 1 1/4" from each framing surface. Center holes in studs. 334.30- NM cable shall be secured with in 12" of boxes and panel. 406.12- All receptacle outlets installed in a residential garage shall be tamper resistant type.
|
ELE13-00256
| Permanent Service | 6/1/2016 | 6/1/2016 | 6/1/2016 2:35:19 PM | P | FAIL |
|
|
Ryan Phone #: ###-#### 250.28- Main bonding jumper shall be installed to ground grounded conductor.
|
ELE13-01291
| Electrical Rough-In | 6/1/2016 | 6/1/2016 | 6/1/2016 2:17:47 PM | P | PASS |
|
|
Contact Brandon for water fountain bonding. Phone #: ###-#### Inspection requested via web by Tony Keen Large fountain perimeter bond rough in ok cover
|
ELE16-01706
| Electrical Rough-In | 5/27/2016 | 6/1/2016 | 6/1/2016 12:03:29 PM | A | PASS |
|
|
Mike// please call 1hr before Phone #: ###-#### Went over HVAC control and boiler controls. Floors 2 and 3 on line. Rough in ok cover
|
ELE16-01333
| Final | 5/31/2016 | 6/1/2016 | 6/1/2016 11:20:31 AM | A | FAIL |
|
|
Hi Rock, Address and corrections have been made. Final inspection please. Contact is David Joseph ###-####. Please call if you have any questions as David will not be on the job site or you can call the office ###-####. Phone #: ###-#### Inspection requested via web by Laura Longshaw Wiring from disconnecting means to x-ray equipment shall be inspected and listing shall be checked. 110.26- Disconnect shall have 30" wide and 36" deep minimum work space in front. -Dedicated electrical space shall be provided from floor to ceiling width and depth of fused electrical disconnect.
|
ELE16-01333
| Permanent Service | 5/31/2016 | 6/1/2016 | 6/1/2016 10:46:08 AM | A | PASS |
|
|
Hi Rock, Permanent Service final inspection please. David Joseph in your contact ###-####. Please call if you have any questions as he will not be on the job site. You can also call the office if you have any questions ###-####. Thank you for everything and have an awesome day. Phone #: ###-#### Inspection requested via web by Laura Longshaw 2nd meter for space D. p/s u/g n ok
|
ELE16-01731
| Temporary Service | 5/31/2016 | 6/1/2016 | 6/1/2016 9:45:17 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Eric Brown t/s o/h n ok
|
ELE13-01291
| Electrical Rough-In | 5/31/2016 | 6/1/2016 | 6/1/2016 9:29:32 AM | A | PASS |
|
|
inspection on water feature bonding Phone #: ###-#### Inspection requested via web by Brandon Robinson 2 smaller fountains perimeter bonds rough in ok cover
|
ELE16-01155
| Final | 6/1/2016 | 6/1/2016 | 6/1/2016 9:07:26 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ESC16-00375
| Random Inspection | 6/1/2016 | 6/1/2016 | 6/1/2016 9:06:21 AM | P | PASS |
|
|
Trash contained, clean job site, OK
|
ESC16-00281
| General Inspection | 6/1/2016 | 6/1/2016 | 6/1/2016 9:05:30 AM | P | PASS |
|
|
Job site clean trash contained. OK
|
ELE16-01153
| Final | 6/1/2016 | 6/1/2016 | 6/1/2016 8:43:49 AM | A | PASS |
|
|
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE16-01134
| Electrical Rough-In | 6/1/2016 | 6/1/2016 | 6/1/2016 12:00:00 AM | A | PASS |
|
|
We are requesting a rough-in inspection for stairway 3 for this afternoon. Our contact is Tony @ ###-#### or Bobby @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Discussed required perimeter bond of pool on upper floor. 2nd floor stair 3 walls rough in ok cover
|