Inspections for the day of: Thursday, June 1, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01656 Final6/1/20176/1/20176/1/2017 2:52:11 PMPPART
Shane is our on site guy ###-####. temp power to the CMCO job trailer Phone #: ###-#### Inspection requested via web by Shawna Gates
Contractor to provide strain relief at top of wall where SOW cable enters conduit to disconnect.
ELE16-03931 Electrical Rough-In6/1/20176/1/20176/1/2017 2:11:50 PMPPASS
coriidors 437A, 437B, 437c Phone #: ###-#### Inspection requested via web by Cathy Duchek
To clarify ELE16-00580 poduim, ELE16-03933 core and shell, ELE16-03932 west fowler, ELE16-03931 east fowler. ELE17-01627 Rex pizza with different address.
Firelid for 437 A, B, C rough in ok cover
ELE16-04108 Final6/1/20176/1/20176/1/2017 1:20:19 PMPPART
Final Inspection for the Gatehouse
Contact Dan Hutchinson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Need complete upstairs lighting, underground for sign and pole lights deeper, receptacle with in 25' of HVAC units north side of building ground level, secure out conduits and disconnects on north side. TCO ok
ELE17-01516 Final5/31/20176/1/20176/1/2017 10:53:57 AMAPASS
Code 12345 Phone #: ###-#### Inspection requested via web by Dean Gernaat
Final ok
ELE17-00852 Electrical Rough-In5/31/20176/1/20176/1/2017 10:53:38 AMAPASS
Call Chris for inspection of hard lid at break room 2nd floor. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Break room hardlid and discussed relocating dampers. They are providing access at new locations. Rough in ok cover
ELE17-01500 Electrical Rough-In5/31/20176/1/20176/1/2017 10:52:20 AMANH
Cover Inspection Phone #: ###-#### Inspection requested via web by Louis Keller
Door locked left message with contractor.
ELE17-00261 Final5/31/20176/1/20176/1/2017 10:03:22 AMAPASS
Garage code 1418 Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE17-00260 Final5/31/20176/1/20176/1/2017 10:02:54 AMAPASS
Garage code 1418 Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE17-01645 Rough-In Permanent Service5/30/20176/1/20176/1/2017 9:33:18 AMAFAIL
New Home inspection, contact name is Travis Phone #: ###-#### Inspection requested via web by Lynn Cable
210.11(C)(3)- Required 20 amp 120 volt circuit for bathroom receptacles shall have no other outlets.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage by nail plates. Up be marked on stud and M closet above switch.
352.6- All PVC fittings shall be listed.
1-piece Cantex expansion joint is not a listed product. Provided by their web site.