ELE17-00627
| Final | 6/1/2017 | 6/1/2017 | 6/1/2017 1:59:42 PM | P | FAIL |
|
|
garage code 1624 Phone #: ###-#### Inspection requested via web by Darryn Coburn Back room by Dining needs AFCI protection and Smoke detector. 2 receps back wall of Dining read open nuetral. Weather proof by A/C not trimmed out. Back patio weather proof dead. Put lock out on Furnace
|
ELE17-01666
| Conference | 6/1/2017 | 6/1/2017 | 6/1/2017 1:16:58 PM | P | DONE |
|
|
Please call me half an hour before inspection so that I can make sure to meet you there. Thank you Phone #: ###-#### Inspection requested via web by Shaun Kirkman Talked about PVC to hot tub under concrete and bonding metal parts within 5ft of tub edge to tub
|
ELE17-01668
| Temporary Service | 6/1/2017 | 6/1/2017 | 6/1/2017 12:54:10 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE17-01672
| Electrical Rough-In | 6/1/2017 | 6/1/2017 | 6/1/2017 12:20:01 PM | P | PASS |
|
|
Dustin Phone #: ###-#### Kitchen/ Back Laundry, bathroom area only ok to cover
|
ELE16-02993
| Final | 5/31/2017 | 6/1/2017 | 6/1/2017 11:39:44 AM | A | PART |
|
|
Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Partial final ok. Waiting on choke for grounding EMT
|
ELE17-01665
| Electrical Rough-In | 5/31/2017 | 6/1/2017 | 6/1/2017 11:01:09 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Don Conley Down bath only rough in ok
|
ELE17-01220
| Permanent Service | 5/31/2017 | 6/1/2017 | 6/1/2017 10:49:02 AM | A | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman Already had perm serv inspection
|
ELE17-00455
| Final | 5/31/2017 | 6/1/2017 | 6/1/2017 10:28:24 AM | A | PASS |
|
|
Call Gary when in route if possible. Phone #: ###-#### Inspection requested via web by Steve McCloy Final ok
|
ELE17-01630
| Rough-In Permanent Service | 5/31/2017 | 6/1/2017 | 6/1/2017 9:45:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon Rough in ok p/s u/g n ok
|