ELE14-00479
| ELE-Aging Inspection | 6/1/2018 | 6/1/2018 | 6/4/2018 1:41:46 PM | | PASS |
|
|
left message on contacts voicemail...requesting to get in contact with Boise City PDS or me to get permit finaled and closed
|
ELE18-01263
| Final | 6/1/2018 | 6/1/2018 | 6/1/2018 1:54:19 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic... 1..outlet in hallway has hot neutral reverse..110.7 2..luminares in closet shall be completely enclosed..410.16(A) 3.. luminares in closet shall have clearances from shelves adhearing to code 410.16(C)
|
ELE18-02021
| Electrical Rough-In | 5/30/2018 | 6/1/2018 | 6/1/2018 1:17:34 PM | P | PASS |
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by cris flores...new grid hallways ok to cover
|
ELE17-02445
| Conference | 6/1/2018 | 6/1/2018 | 6/1/2018 11:18:13 AM | P | PASS |
|
|
discussed outlets above ceiling grid discussed clearances for disconnects on roof units with gas piping in front of...ok'd by Tom discussed requirements for service inspection
|
ELE17-03198
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 11:11:49 AM | A | FAIL |
|
|
Lock code 4825 Phone #: ###-#### Inspection requested via web by Ryan Wake... 1. all outlets in garage shall have GFCI protection 2. damp location rated shower can trim needs installed in shower
|
ELE18-01909
| Electrical Rough-In | 5/31/2018 | 6/1/2018 | 6/1/2018 10:09:39 AM | A | PASS |
|
|
Chad VanOrden is contact at ###-####. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce...walls only ok to cover
|
ELE18-02052
| Electrical Rough-In | 5/31/2018 | 6/1/2018 | 6/1/2018 9:44:21 AM | A | PASS |
|
|
Underground inspection any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller...ok to cover
|
ELE18-00397
| Electrical Rough-In | 5/31/2018 | 6/1/2018 | 6/1/2018 9:12:24 AM | A | PASS |
|
|
Rough in of back of house interior walls Phone #: ###-#### Inspection requested via web by Tom Jenkins...verified ground screws in all boxes...all walls ok to cover at this time
|
ELE18-01235
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 8:36:46 AM | A | PASS |
|
|
code 1234 ANY ? CALL BILL ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn....ok to final
|