Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00479 ELE-Aging Inspection6/1/20186/1/20186/4/2018 1:41:46 PM PASS
left message on contacts voicemail...requesting to get in contact with Boise City PDS or me to get permit finaled and closed
ELE18-01263 Final6/1/20186/1/20186/1/2018 1:54:19 PMPFAIL
Phone #: ###-#### Inspection requested via web by Hidajet Zahic...
1..outlet in hallway has hot neutral reverse..110.7
2..luminares in closet shall be completely enclosed..410.16(A)
3.. luminares in closet shall have clearances from shelves adhearing to code 410.16(C)
ELE18-02021 Electrical Rough-In5/30/20186/1/20186/1/2018 1:17:34 PMPPASS
Ceiling cover Phone #: ###-#### Inspection requested via web by cris flores...new grid hallways ok to cover
ELE17-02445 Conference6/1/20186/1/20186/1/2018 11:18:13 AMPPASS
discussed outlets above ceiling grid
discussed clearances for disconnects on roof units with gas piping in front of...ok'd by Tom
discussed requirements for service inspection
ELE17-03198 Final5/31/20186/1/20186/1/2018 11:11:49 AMAFAIL
Lock code 4825 Phone #: ###-#### Inspection requested via web by Ryan Wake...
1. all outlets in garage shall have GFCI protection
2. damp location rated shower can trim needs installed in shower
ELE18-01909 Electrical Rough-In5/31/20186/1/20186/1/2018 10:09:39 AMAPASS
Chad VanOrden is contact at ###-####. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce...walls only ok to cover
ELE18-02052 Electrical Rough-In5/31/20186/1/20186/1/2018 9:44:21 AMAPASS
Underground inspection any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller...ok to cover
ELE18-00397 Electrical Rough-In5/31/20186/1/20186/1/2018 9:12:24 AMAPASS
Rough in of back of house interior walls Phone #: ###-#### Inspection requested via web by Tom Jenkins...verified ground screws in all boxes...all walls ok to cover at this time
ELE18-01235 Final5/31/20186/1/20186/1/2018 8:36:46 AMAPASS
code 1234 ANY ? CALL BILL ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn....ok to final