BLD17-04479
| FIRE-Final Inspection | 6/1/2018 | 6/1/2018 | 6/1/2018 2:28:36 PM | P | FAIL |
|
|
Need sign offs on the project related fire alarm and fire sprinkler permits. Need the three missing exit discharge lights installed and tested. Need the emergency lights marked on the city approved plans repaired and tesed
Dave Phone #: 208-###-####
|
FIR18-00379
| INSP-Final Inspection | 5/29/2018 | 6/1/2018 | 6/1/2018 2:25:28 PM | P | FAIL |
|
|
Plan mods are needed showing the self contained Pre-action system and the required smoke detector over it. Need the communicator shown and approved. Please show all changes and have approved by the engineer of record since fire alarm plans/design is shown on the "E" sheets in the city approved building drawings.
CSL Plasma Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR18-00129
| INSP-Final Inspection | 5/29/2018 | 6/1/2018 | 6/1/2018 2:18:22 PM | P | FAIL |
|
|
Need 200lb test and 24 hour air test and the interconnects with the fire alarm panel tested.
Contact Anrew Larson - ###-#### 30 Min prior to Fire Final Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00074
| INSP-Final Inspection | 5/31/2018 | 6/1/2018 | 6/1/2018 11:10:48 AM | A | FAIL |
|
|
Suppression system functioned but the appliances do not fit under the hood and the partition is missing between the fryer and four burner stove.
Dave Phone #: ###-####
|
FIR18-00076
| INSP-Final Inspection | 5/31/2018 | 6/1/2018 | 6/1/2018 11:09:35 AM | A | PASS |
|
|
Permit finaled
Dave Phone #: ###-####
|
FIR18-00075
| INSP-Final Inspection | 5/31/2018 | 6/1/2018 | 6/1/2018 11:09:14 AM | A | PASS |
|
|
Permit finaled
Dave Phone #: ###-####
|
BLD18-01672
| FIRE-Final Inspection | 6/1/2018 | 6/1/2018 | 6/1/2018 11:06:39 AM | P | PASS |
|
|
life safety passed
Dennis Phone #: ###-####
|
FIR18-00221
| INSP-Final Inspection | 5/31/2018 | 6/1/2018 | 6/1/2018 11:00:26 AM | A | FAIL |
|
|
As-builts are needed showing the candella changes and address changes. One strobe is missing as noted on the plans. For a final the notification circuit needs tested, as-builts, correct batteries, document box, breaker lock, manual pull stations in the adjacent restraunt relocated and tested.
|
FIR17-00522
| INSP-Sprinkler Rough-in | 5/31/2018 | 6/1/2018 | 6/1/2018 10:51:16 AM | A | PART |
|
|
first floor hallway and rooms with grid are ok for cover. I noted that a pendant will need to be added in a closet as discussed and two heads are overspaced in the corridor. I will check these at the next inspection.
|
FIR12-00474
| INSP-Final Inspection | 5/31/2018 | 6/1/2018 | 6/1/2018 7:50:33 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Jeff Packham
|
BLD17-03385
| FIRE-Final Inspection | 5/31/2018 | 6/1/2018 | 6/1/2018 7:50:05 AM | A | PASS |
|
|
Life safety passed. A separate racking permit has been submitted.
Bob Phone #: ###-####
|
FIR18-00221
| INSP-Final Inspection | 5/31/2018 | 6/1/2018 | 5/31/2018 3:45:39 PM | P | CANC |
|
|
Tony Burtlow is our Technician on site. Phone #: ###-#### >> Inspection requested via web by David Oliver Inspection cancelled from web by: David Oliver
|