MEC18-02404
| Final | 5/29/2018 | 6/1/2018 | 6/1/2018 4:30:43 PM | P | FAIL |
|
|
INSTALLER JESSE ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 3/4 condensate drain outside needs a 90 turned down
|
MEC18-02463
| Final | 6/1/2018 | 6/1/2018 | 6/1/2018 3:58:29 PM | P | FAIL |
|
|
please call first to make sure someone is there. Gas pressure test. Flue pressure test. furnace and ac install. Phone #: ###-#### Inspection requested via web by jeremy wanders - ac breaker size is too large- lineset penetration needs to be sealed- need electrical done on furnace- eletrical permit needed for work on furnace
|
MEC18-02463
| Pressure Test | 6/1/2018 | 6/1/2018 | 6/1/2018 3:51:53 PM | P | PASS |
|
|
please call first to make sure someone is there. Gas pressure test. Flue pressure test. furnace and ac install. Phone #: ###-#### Inspection requested via web by jeremy wanders - 20lb gas pass
|
MEC18-02392
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 3:17:02 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- lineset penetration needs to be sealed- condensate drain for indoor coil needs a 90 at the termination point outside and needs to be sloped for drainage.
|
MEC17-05533
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 2:36:57 PM | P | FAIL |
|
|
AC: 1406 Phone #: ###-#### Inspection requested via web by Gary Reeves- condensate drain for upstairs unit is missing- need a duct blast report on upstairs unit- need updated Man J for upstairs unit- lineset penetration on west side needs sealed
|
MEC17-04141
| Final | 6/1/2018 | 6/1/2018 | 6/1/2018 1:25:44 PM | P | PASS |
|
|
line sets have UV protection and are supported- final ok
|
MEC18-02424
| Rough-in | 5/31/2018 | 6/1/2018 | 6/1/2018 1:14:02 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Stegemann-clearances from top opening of fireplace to bottom of mantel are too small. Manual says that a mantel over hang of 9.5 inches needs to be 9.5 inches above top opening of fireplace
|
MEC18-01006
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 11:54:31 AM | P | PASS |
|
|
Site Contact: Aaron Roberts. Mechanical Final Inspection Phone #: ###-#### Inspection requested via web by RM Mechanical- final ok suite 110 gridline a-c
|
MEC17-04141
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 10:55:33 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- SW linesets outside need UV protection and supported to wall
|
MEC17-04142
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 10:49:37 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- bathroom exhaust fan not finished- NW hardlid supply grilles not finished- furnace condensate pan outlet needs plugged and sealed- condensate line in attic needs supported- lineset in attic needs supported- lineset needs UV protection at outdoor unit
|
MEC17-04268
| DOC - Permit Finaled | 6/1/2018 | 6/1/2018 | 6/1/2018 10:08:31 AM | P | PASS |
|
|
final ok
|
MEC17-04268
| Mec-Aging Inspection | 6/1/2018 | 6/1/2018 | 6/1/2018 10:07:45 AM | | CANC |
|
|
|
MEC18-02143
| Final | 5/30/2018 | 6/1/2018 | 6/1/2018 9:33:16 AM | A | FAIL |
|
|
Please call Mike the owner when in route to home ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd - need to witness 5 lb flue pressure test- need to cut another combustion air vent in door 12" from the top
|
MEC18-02240
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 8:46:49 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- no access
|
MEC18-02168
| Final | 5/31/2018 | 6/1/2018 | 6/1/2018 8:36:43 AM | A | PASS |
|
|
Bob heat and air inspection Phone #: ###-####- final ok
|