ELE19-04502
| Electrical Rough-In | 6/1/2020 | 6/1/2020 | 6/1/2020 2:28:47 PM | P | PASS |
|
|
L3 PT deck pour #2 Call Craig ( Could Do AM inspection it is ready) Phone #: ###-#### Inspection requested via web by Tom Betty Pour noted rough in ok cover.
|
ELE20-01787
| Final | 5/29/2020 | 6/1/2020 | 6/1/2020 1:39:37 PM | P | PASS |
|
|
This is the Owyhee tavern patio. Please call in advance so I can meet you there with a ladder. Thanks Rex Phone #: ###-#### Inspection requested via web by Rex Boyles Final ok
|
ELE20-01787
| Electrical Rough-In | 6/1/2020 | 6/1/2020 | 6/1/2020 1:36:22 PM | P | PASS |
|
|
This is the Owyhee tavern patio. Please call in advance so I can meet you there with a ladder. Thanks Rex Phone #: ###-#### Inspection requested via web by Rex Boyles All wiring and conduits surface mounted on exterior. Switched power for lights and drapes rough in ok.
|
ELE20-01807
| Final | 5/29/2020 | 6/1/2020 | 6/1/2020 1:10:19 PM | P | PASS |
|
|
Please call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Final ok
|
ELE20-01807
| Electrical Rough-In | 6/1/2020 | 6/1/2020 | 6/1/2020 1:05:26 PM | P | PASS |
|
|
Please call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Change out furnace, installed dedicated circuit and receptacle for condensate pump rough in ok.
|
ELE20-01835
| Final | 5/29/2020 | 6/1/2020 | 6/1/2020 1:03:51 PM | P | PASS |
|
|
Please call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Final ok
|
ELE20-01835
| Electrical Rough-In | 6/1/2020 | 6/1/2020 | 6/1/2020 12:47:04 PM | P | PASS |
|
|
Please call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Rough in of AC and service receptacle rough in ok.
|
ELE19-03913
| Electrical Rough-In | 6/1/2020 | 6/1/2020 | 6/1/2020 12:19:47 PM | P | PASS |
|
|
Requesting 10:00 am inspection time. Install one emc over enterance into Jump Parking gargae on 11th street. Phone #: ###-#### Inspection requested via web by Ken Olsen Listing and disconnecting means confirmed. Rough in ok.
|
ELE20-01395
| Rough-In Permanent Service | 5/29/2020 | 6/1/2020 | 6/1/2020 11:31:34 AM | A | FAIL |
|
|
It will be open. If you have any questions please feel free to contact Kaiden ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.3- Acorn clamp located in garage concrete encased electrode shall be installed as per manufacturers instructions. GEC located under bolt. Recessed can j-box covers shall be installed tight to boxes. up bath and top of stairs. 250.32- Seperate structures shall have a grounding electrode conductor installed. 250.50- All grounding electrodes present shall be used. Concrete encased electrode located under window in basement. 314.17(C)- NM cable sheathing shall enter box a minimum of 1/4" at down bed smoke detector. 1712 partially foam sealed, asked insulators to leave. 1710 not started foam seal.
|
ELE20-01393
| Rough-In Permanent Service | 5/29/2020 | 6/1/2020 | 6/1/2020 11:21:30 AM | A | FAIL |
|
|
It will be open. If you have any questions please feel free to contact Kaiden ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.3- Recessed can j-fox covers shall be installed tight to box. Up living rm, up bath. 250.68- Concrete encased connection shall remain accessible located at house behind door. 334.30 NM cable shall be scured with in 12" of south oudoor receptacle box.
|
ELE20-01799
| Rough-In Permanent Service | 5/29/2020 | 6/1/2020 | 6/1/2020 9:46:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard Rough in ok cover p/s u/g n ok
|
ELE20-01828
| Rough-In Permanent Service | 5/31/2020 | 6/1/2020 | 6/1/2020 8:58:47 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic Rough in ok cover p/s o/h n ok
|