| INSP-Sprinkler Rough-in | 6/1/2020 | 6/1/2020 | 6/1/2020 3:22:03 PM | P | CANC |
|
|
Gabe Garduno is the contact Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00313
| INSP-Sprinkler Rough-in | 5/29/2020 | 6/1/2020 | 6/1/2020 1:50:24 PM | A | PART |
|
|
Todays inspection was for the three groups of six apartments starting from the east end. Rough-in passed but four pendant needs to be relocated as discussed. Two sidewall heads need to be installed, per plan, under the intermediate laddings as discussed. Piping at the fur down in these three groups of six can be covered. No piping on the third floor can be covered until a tenting inspection has been passed. Cam is going to provide as-builts with the additional 90's included in calcs as discussed and the possible deletion of heads at the landings.
Cam Hess is the contact (: Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00790
| INSP-Sprinkler Rough-in | 5/29/2020 | 6/1/2020 | 6/1/2020 12:00:00 AM | A | CANC |
|
|
screened // Tanner Phone #: ###-####
|