Inspections for the day of: Wednesday, June 10, 1998.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD97-01324 INSP-Sprinkler Rough-in/Hydro6/9/19986/10/19986/10/1998 12:00:00 AMAPASS
hydro testing/ ###-#### jenifer hydro okay. heads installed in stairs. riser room has numerous pentrations - doesn't meet 1 hour - they aren't finished with room
BLD98-00739 INSP-Final Inspection6/10/19986/10/19986/10/1998 12:00:00 AMPPART
final/ doug/ security desk/ strobe wrong candela - must be 60 minimum for room
BLD98-01200 INSP-Final Inspection6/9/19986/10/19986/10/1998 12:00:00 AMPFAIL
RICK ###-#### PAGER rough-in only. numerous pentrations in lid. head needed by janitor closet. turn heads up in corridor south of leased space
BLD98-01399 INSP-Final Inspection6/9/19986/10/19986/10/1998 12:00:00 AMPFAIL
RICK ###-#### rough-in only. numerous pentrations in lid over tenant and corridor lid.