ELE02-00674
| Final | 6/3/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 06/03/2002 at 13:05:53. Contact: ###-####. ok 6/10/2002 10:34:34 AM
|
ELE02-01685
| Electrical Rough-In | 6/7/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | A | FAIL |
|
|
###-#### rex cor. posted called 314.16 box fill 400-8(5) no cords above ceiling, 348-30 shall secure flex, 300-15 (c) install a bushing in flex for abrasion 6/10/2002 12:00:16 PM
|
ELE02-00986
| Final | 6/7/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | A | PASS |
|
|
key is under front door mat alison ###-####-re-insp ok 6/10/2002 11:35:31 AM
|
ELE02-00173
| Final | 6/7/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 06/07/2002 at 16:31:36. Contact: ###-####. needs outlet for wall space left of cabinet where you enter house label panels and install blank cover called 6/10/2002 5:38:40 PM
|
ELE02-01436
| Electrical Rough-In | 6/10/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 06/10/2002 at 07:40:10. Contact: ###-####. called need to meet contractor at job site some corrections , will post after meeting with contractor 6/10/2002 6:18:38 PM
|
ELE02-01726
| Rough-In Permanent Service | 6/10/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | FAIL |
|
|
john ###-####--r/i & ser cor. posted called 210.52 (A&B) needs outlets on 20 kit circuit foo feed outlets, in dinning rm and breakfast nook, 314.20 outside boxes not flush 210.52(F) & 210.11(C) all outlets in laundry area, shall be 20 amp laundry circuit, 300.4 11/4 inches needed see added p/s inspection for info 6/10/2002 3:10:35 PM
|
ELE02-01722
| Permanent Service | 6/10/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | PASS |
|
|
###-####
p/s u/g rec. ok 6/10/2002 4:03:21 PM
|
ELE02-00920
| Final | 6/10/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | PASS |
|
|
fn gene- -###-#### ok 6/10/2002 6:36:58 PM
|
ELE02-01340
| Permanent Service | 6/10/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | FAIL |
|
|
for homeowner call 1st before insp- ###-####-ellen all correcdtion s not made called need to grd to u/g water pipe within 5 ft of where it enters or verify that there is less than 10 ft of metal u//g water pipe in contact with earth 6/10/2002 5:01:39 PM
|
ELE02-01726
| Permanent Service | 6/10/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | PASS |
|
|
p/s u/g new ok
|
ELE01-03617
| Electrical Rough-In | 6/10/2002 | 6/10/2002 | 6/10/2002 12:00:00 AM | P | PART |
|
|
concrete encased electrode ok
|