FIR03-00103
| FIR-Aging Inspection | 6/10/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | | FAIL |
|
|
I spoke to Randy at Debest and he stated that the work is done. I told him that I will need access to the building to verify. He will set up 6/10/2003 1:54:24 PM
|
FIR03-00226
| INSP-Sprinkler Rough-in/Hydro | 6/10/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | A | PASS |
|
|
sprinkler piping is ok to cover
|
FIR02-00500
| INSP-Final Inspection | 6/6/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | A | FAIL |
|
|
provide signs on the riser room and fire alarm room doors and provide maps for initiating devices and facp location at the nurses station 6/10/2003 10:37:10 AM
|
FIR03-00116
| INSP-Alarm Testing | 6/9/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | A | CANC |
|
|
inspection was for tomorrow not today 6/10/2003 8:22:24 AM
|
FIR03-00116
| INSP-Final Inspection | 6/9/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | A | CANC |
|
|
inspection was for tomorrow not today 6/10/2003 8:22:39 AM
|
BLD02-01148
| FIRE-Final Inspection | 6/9/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | A | PASS |
|
|
steve; Phone #: ###-#### Fire life safety finaled. Structural to verify that the janitor closet door hardware gets changed out to approved type 6/10/2003 1:53:08 PM
|
FIR03-00170
| INSP-Sprinkler Rough-in/Hydro | 6/9/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | A | PASS |
|
|
work has already been completed. See FIR03-00226 6/10/2003 11:36:47 AM
|
FIR03-00254
| INSP-Sprinkler Rough-in/Hydro | 6/10/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | P | FAIL |
|
|
pendant head in storage room 004 is too close to surface mount light fixture. Pendant head at recpt/sec 005 is too close to wall. Verify there is a pendant in the locked mechanical room 044 6/10/2003 2:30:27 PM
|
BLD02-02701
| FIRE-Final Inspection | 6/10/2003 | 6/10/2003 | 6/10/2003 12:00:00 AM | P | PASS |
|
|
fire life 6/10/2003 3:33:34 PM safety finaled 6/10/2003 3:33:48 PM
|