Inspections for the day of: Friday, June 10, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02027 Temporary Service6/10/20056/10/20056/10/2005 3:46:25 PMPPASS
MOVED GRND. TO NEUTRAL BUS IN METER AS PER REQUIREMENT.; Phone #: ###-#### Internet Inspection Request from: dennis mcneely t/s u/g new ok
ELE05-00963 Final6/10/20056/10/20056/10/2005 2:52:39 PMPFAIL
brian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called correct reversed polarity fam rm right of bedrm door, 210.52(A) shall provide required outlet spacing where closet was removed after r/i inspection in fam rm N E corner
ELE05-01969 Temporary Service6/9/20056/10/20056/10/2005 2:15:08 PMPPASS
Scheduled by a contractor via Hello! on 6/9/2005 at 9:51:20 AM. Contact: ###-####. t/s u/g new ok
ELE05-00711 Final6/10/20056/10/20056/10/2005 2:05:09 PMPPASS
jim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie final ok
ELE05-02048 Permanent Service6/10/20056/10/20056/10/2005 1:31:00 PMPPASS
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
p/s u/g new ok
ELE05-02047 Electrical Rough-In6/9/20056/10/20056/10/2005 12:34:43 PMAFAIL
Please meet with Scott or Chuck (####-####) They will show you the new machine and any other work that needs inspected. Thank you.; Phone #:###-#### Internet Inspection Request from: BRIAN KEITH cor. posted called 314.23(H)(1) shall use boxes with hubs for pendant boxes, 110.2 equip shall be listed, 250.97 shall use bond bushing where concentric, eecentric KOs and encounted for bonding over 250 volts to grd, 408.4 label all circuits at panels and switchboards
ELE05-00459 Final6/9/20056/10/20056/10/2005 10:31:52 AMAPASS
henry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok corrections made
ELE04-02398 Final6/9/20056/10/20056/10/2005 8:54:12 AMAFAIL
mark; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted met owner 210.8 needs working gdci in M bath, needs inuse cover outside, and owner needs electrical contractor to secure permit and wire hot tub, or remove all wiring owner installed when he wire hot tub
ELE05-02048 Electrical Rough-In6/10/20056/10/20056/10/2005 12:00:00 AMPFAIL
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called u/g for parking lot lights covered before inspection