ELE05-02058
| Rough-In Permanent Service | 6/10/2005 | 6/10/2005 | 6/10/2005 3:58:10 PM | P | PASS |
|
|
###-#### verna ric ok p/s u/g n ok
|
ELE05-02051
| Rough-In Permanent Service | 6/10/2005 | 6/10/2005 | 6/10/2005 3:57:05 PM | P | PASS |
|
|
ron ###-#### ric ok p/s u/g n ok
|
ELE05-01226
| Final | 6/10/2005 | 6/10/2005 | 6/10/2005 3:01:07 PM | P | PASS |
|
|
allan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final
|
ELE05-02060
| Electrical Rough-In | 6/10/2005 | 6/10/2005 | 6/10/2005 1:31:22 PM | P | PASS |
|
|
###-#### john met elect, they are ensuring 24" burial depth at boxes. ok to cover from island to south. We need to see from island to store at later time.
|
ELE05-01533
| Permanent Service | 6/10/2005 | 6/10/2005 | 6/10/2005 1:27:31 PM | P | PASS |
|
|
p/s exst meter pak, #106 n ok
|
ELE05-01479
| Conference | 6/9/2005 | 6/10/2005 | 6/10/2005 10:16:59 AM | A | DONE |
|
|
for homeowner cell ###-####- steve --call 1st before insp talked about broken boxes, grounding, make-up, stapling, length of free conductor
|
ELE05-02046
| Temporary Service | 6/9/2005 | 6/10/2005 | 6/10/2005 10:00:48 AM | A | PASS |
|
|
tom ###-#### t/s u/g n ok
|
ELE05-00348
| Final | 6/9/2005 | 6/10/2005 | 6/10/2005 9:30:59 AM | A | PASS |
|
|
please call for access codes///jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, ok to final
|
ELE05-01706
| Electrical Rough-In | 6/9/2005 | 6/10/2005 | 6/10/2005 8:30:38 AM | A | PASS |
|
|
UNDERGROUND CONDUIT, PLEASE CALL AFTER INSPECTION SO WE CAN SCHEDULE BACK FILL; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contr, ok to cover u/g for parking lot lites only
|
ELE05-02038
| Rough-In Permanent Service | 6/9/2005 | 6/10/2005 | 6/10/2005 8:12:40 AM | A | FAIL |
|
|
shawn ###-#### called, left message, left corr notice, 300.4(A)(1) edge of hole shall be 1 1/4" from edge of framing member, 300.4(B) (D) nm cable shall be 1 1/4" from edge of framing member, 312.5 gec shall have abrasion protection, 110.12(A) box shall have un-used openings closed,210.52(C)(10 kitchen outlets shall be max 24", 210.52(H) hall shall have recpt if over 10',210.52(A)(2) 2' wall shall have recpt by utility, dining room, 334.80 shall derate bundled cable over panel, 110.14(A) terms for more than 1 conductor shall be identified,BCC job id sticker shall be posted, approved set of plans shall be on job
|