Inspections for the day of: Tuesday, June 10, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00855 FIRE-Final Inspection6/10/20086/10/20086/10/2008 6:12:10 PMPNR
Discussed shell building requirements regarding fire life safety issues.
FIR08-00361 INSP-Sprinkler Rough-in/Hydro6/9/20086/10/20086/10/2008 4:04:49 PMAFAIL
Sprinkler heads at each first floor unit under the stairways are overspaced, 2nd floor mid unit hallway head needs relocated due to overspacing, remainder of flow testing passed, tenting at the attic spaces is satisfactory.
BLD08-00956 FIRE-Conference6/9/20086/10/20086/10/2008 3:47:04 PMADONE
Rob- fire life saftey Phone #: ###-####
BLD08-00127 FIRE-Final Inspection6/10/20086/10/20086/10/2008 2:36:13 PMAPASS
Fire life safety inspection passed, HVAC unit duct detectors tested okay.
FIR07-00879 INSP-Supply line flush6/9/20086/10/20086/10/2008 1:34:06 PMAPART
UG fire supply line flush completed satisfactory.
FIR08-00301 INSP-Final Inspection6/10/20086/10/20086/10/2008 12:47:00 PMPPASS
Scope of work is complete, fire sprinkler permit finaled.
FIR07-00879 INSP-Sprinkler Rough-in/Hydro6/9/20086/10/20086/10/2008 12:43:43 PMAPART
UG hydrostatic test passed.
BLD08-00895 FIRE-Final Inspection6/10/20086/10/20086/10/2008 12:41:29 PMPPASS
C/N items verified for compliance, fire life safety finaled.
BLD08-00011 FIRE-Final Inspection6/9/20086/10/20086/10/2008 12:40:13 PMAPASS
Correction notice items per previous fire life safety inspection are finished, racking has been removed, one exit sign at the office repaired while on site, inspection passed. NOTE: Contractor has misplaced the request for occupancy signature card-not available on site for sign off.
BLD07-02391 FIRE-Final Inspection6/9/20086/10/20086/10/2008 12:35:48 PMAPART
The exit sign/EM light and PFE have been installed per correction notice, final pending plan modification for now unfinished portions of the building including the east HVAC duct detector which is not powered at this time.
FIR08-00281 INSP-Sprinkler Rough-in6/9/20086/10/20086/10/2008 12:32:44 PMAPART
UG fire supply line, PIV, remote FDC piping and ductile stub in at the riser are okay for cover, portions of piping already concealed were uncovered and exposed on site per request, line bedding is acceptable.