Inspections for the day of: Tuesday, June 10, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01003 FIRE-Conference6/10/20086/10/20086/11/2008 3:42:38 PMPDONE
I went over project phasing with Mark.
FIR08-00389 INSP-Final Inspection6/10/20086/10/20086/11/2008 12:27:14 PMPPASS
Permit finaled
BLD08-01165 FIRE-Final Inspection6/10/20086/10/20086/10/2008 4:45:11 PMPPASS
life safety passed
BLD05-01602 FIRE-Final Inspection6/10/20086/10/20086/10/2008 3:31:50 PMPPASS
Fire life safety passed.
FIR07-00999 INSP-Final Inspection6/10/20086/10/20086/10/2008 3:30:55 PMPPASS
permit finaled
FIR07-00999 INSP-Alarm Testing6/9/20086/10/20086/10/2008 3:30:21 PMPPASS
Permit finaled
FIR07-00886 INSP-Final Inspection6/9/20086/10/20086/10/2008 1:34:28 PMPPASS
Permit finaled
BLD08-01007 FIRE-Final Inspection6/9/20086/10/20086/10/2008 1:31:22 PMAPART
A temporary occupancy was given with Mark Sentenno's permission until the remaining insulation issues in the strip mall have been addressed by Oppenhiemer Development.
FIR07-00874 INSP-Sprinkler Rough-in6/9/20086/10/20086/10/2008 1:29:01 PMADONE
This inspection was actually for a conference regarding the light fixtures blocking the pendant sprinkler spray. Grinnell did not show up for the conference but the superintendant for Petra was there and he made a copy of the Beam Rule spacing chart in NFPA 13 cahpter 8. We measured a couple of heads so that he knew what I was looking at.
FIR07-00309 INSP-Sprinkler Rough-in/Hydro6/9/20086/10/20086/10/2008 12:41:01 PMAPASS
Rough-in passed except a pendant head in the upper floor restroom is blocked by a stub wall. Will need a separate inspection when the tenting is done. Nick Anderson provided revised hydraulic calculations for the side wall head in the lower level bedroom #2 proving it could be spaced in the 6" top 12" window.
FIR08-00115 FIR-Aging Inspection6/10/20086/10/20086/10/2008 10:33:02 AM NR
work is in progress
BLD08-00125 FIRE-Final Inspection6/10/20086/10/20086/10/2008 10:03:54 AMPPASS
fire life safety passed
FIR08-00231 INSP-Final Inspection6/9/20086/10/20086/10/2008 10:03:18 AMAPASS
Permit finaled
FIR08-00396 INSP-Final Inspection6/9/20086/10/20086/10/2008 7:41:25 AMAPASS
Permit finaled
FIR08-00358 INSP-Final Inspection6/10/20086/10/20086/10/2008 12:00:00 AMPCANC
ben Phone #: ###-####