Inspections for the day of: Wednesday, June 10, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDixie Fellows
TitleMEC-COM/RES INSPECTOR
Phone #794-6208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS09-00056 MIS-Aging Inspection6/10/20096/10/20096/11/2009 11:53:30 AM PASS
MEC09-01281 Rough-in6/9/20096/10/20096/10/2009 4:23:52 PMAFAIL
ANY QUESTIONS CALL DOUG ANDERSON AT ###-####. THANK YOU. Phone #: ###-#### Internet Inspection Request from: Doug worden...no access
MEC09-01150 Rough-in6/10/20096/10/20096/10/2009 4:23:24 PMPFAIL
bj...need clearance at back of f/p from insulation
MEC09-01150 Pressure Test6/10/20096/10/20096/10/2009 4:22:46 PMPPASS
brandon - please call 1/2 prior for access Phone #: ###-####...20lb gas to f/p ok
MEC09-01224 Rough-in6/9/20096/10/20096/10/2009 3:36:13 PMAPART
Pressure Test also, please Phone #: ###-#### Internet Inspection Request from: GREG ANDERSEN..gas ok..left c/n on window
MEC09-01262 Final6/9/20096/10/20096/10/2009 3:13:23 PMPPASS
Please inspect as late in the afternoon as possible. Call with any problems. Thanks, April. Phone #: ###-#### Internet Inspection Request from: April Sims
MEC08-03029 Final6/9/20096/10/20096/10/2009 2:49:54 PMAFAIL
Lars Please call first for access code Phone #: ###-####..need secondary drain at furnace..raise line-set out of dirt..gas flex connector at furnace undersized..need outside gas shut off at f/p
MEC09-01219 Rough-in6/10/20096/10/20096/10/2009 11:36:35 AMPPART
also type 1 hood grease duct//Mike ###-####...heating side of job r/i ok..hood and duct info on other inspection
MEC09-00141 Rough-in6/10/20096/10/20096/10/2009 11:35:09 AMAPART
Perform light test for kitchen hood duct. Phone #: ###-#### Internet Inspection Request from: Jason King..light test ok..need hood installers idaho state contractors number..checking with lee regarding top of hood protection..and clean-out in vertical run of grease duct
MEC09-01219 Rough-in6/9/20096/10/20096/10/2009 11:31:02 AMACANC
Dave Phone #: ###-####...grease hood welds and wrap ok...hood ok