Inspections for the day of: Wednesday, June 10, 2009.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00247 INSP-Sprinkler Rough-in/Hydro6/9/20096/10/20096/10/2009 3:41:05 PMPPART
Todays inspection was a rough-in. See the city approved plans for the corrections required which include an overspaced head, a pendant that needs to be supplied from its own mechanical tee, additional hangers on the 2" anti-freeze supply piping and resubmittals showing the anti-freeze system in the front entry canopy and the modifications at the wash bay.
FIR08-00810 INSP-Final Inspection6/9/20096/10/20096/10/2009 2:12:50 PMAPASS
permit passed
FIR08-00603 INSP-Final Inspection6/9/20096/10/20096/10/2009 2:12:29 PMAPASS
permit passed