FIR09-00247
| INSP-Sprinkler Rough-in/Hydro | 6/9/2009 | 6/10/2009 | 6/10/2009 3:41:05 PM | P | PART |
|
|
Todays inspection was a rough-in. See the city approved plans for the corrections required which include an overspaced head, a pendant that needs to be supplied from its own mechanical tee, additional hangers on the 2" anti-freeze supply piping and resubmittals showing the anti-freeze system in the front entry canopy and the modifications at the wash bay.
|
FIR08-00810
| INSP-Final Inspection | 6/9/2009 | 6/10/2009 | 6/10/2009 2:12:50 PM | A | PASS |
|
|
permit passed
|
FIR08-00603
| INSP-Final Inspection | 6/9/2009 | 6/10/2009 | 6/10/2009 2:12:29 PM | A | PASS |
|
|
permit passed
|