Inspections for the day of: Thursday, June 10, 2010.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01364 ELE-Aging Inspection6/10/20106/10/20106/14/2010 6:25:37 AM DONE
suc
ELE09-01351 ELE-Aging Inspection6/10/20106/10/20106/14/2010 6:24:49 AM DONE
suc
ELE09-01016 ELE-Aging Inspection6/10/20106/10/20106/14/2010 6:23:22 AM DONE
see final
ELE10-01142 Final6/10/20106/10/20106/10/2010 3:40:36 PMPPASS
Tile guy should be working there this afternoon Inspection requested from web by: Barbara Szurgot Phone #: ###-#### ok to final
ELE10-01251 Permanent Service6/10/20106/10/20106/10/2010 2:54:52 PMPPASS
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called contractor, corrections made, left red tag to remove illegal temp receptacle out back, p/s o/h rec ok
ELE10-01100 Rough-In Permanent Service6/9/20106/10/20106/10/2010 1:36:45 PMPPASS
please call when on way//Chad Phone #: ###-#### met contractor, check for clearance at service at final, ric ok, p/s o/h rec ok
ELE10-01173 Electrical Rough-In6/10/20106/10/20106/10/2010 12:40:50 PMPFAIL
Rough in of bathrooms and electrical panel in new tenant space. Inspection requested from web by: Steve Craig Phone #: ###-#### called, gave corrections to provide nail plates, strap mc and provide 1 1/4" for flex, add mud ring, strap conduit at meter, fix and recall
ELE10-00993 Final6/9/20106/10/20106/10/2010 10:47:52 AMAPASS
Inspection requested from web by: Rowdy Monroe Phone #: ###-#### ok to final
ELE10-01243 Final6/8/20106/10/20106/10/2010 10:26:10 AMANH
bring kitchen to code Inspection requested from web by: Randy Fletcher Phone #: ###-#### called, left card, fee due
ELE10-01160 Electrical Rough-In6/10/20106/10/20106/10/2010 10:01:04 AMAPASS
Inspection requested from web by: Terry Scott ric ok
ELE10-01260 Electrical Rough-In6/9/20106/10/20106/10/2010 9:36:52 AMACANC
Inspection requested from web by: Erick Baker Phone #: ###-#### wrong type request, see rip
ELE10-01260 Rough-In Permanent Service6/10/20106/10/20106/10/2010 9:36:40 AMAPASS
Inspection requested from web by: Erick Baker Phone #: ###-#### ri ok, p/s o/h n ok
ELE10-01264 Permanent Service6/10/20106/10/20106/10/2010 9:14:34 AMAPASS
Inspection requested from web by: Robert Waite Phone #: ###-#### met contractor, will call for final later, must get clearances for house panel or will take further action, service is conditional, p/s o/h n ok
ELE10-01264 Final6/9/20106/10/20106/10/2010 9:01:50 AMACANC
Inspection requested from web by: Robert Waite Phone #: ###-#### wrong type request, see p/s
ELE10-01229 Electrical Rough-In6/10/20106/10/20106/10/2010 8:55:03 AMPCANC
eric- trench Phone #: ###-#### Inspection cancelled from web by: Letitia Gallop//Bernice called to cancel inspection on 6/10/10 at 8:56am
ELE10-01251 Permanent Service6/9/20106/10/20106/10/2010 8:22:12 AMAFAIL
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called, left correction notice, NEC 250.52(A)(1) shall utilize u/g water water pipe for grounding electrode, 110.12(A) shall close unused openings, 334.30 shall secure nm cables within 12" of box, left correction notice to owner about electrical work
ELE08-01144 ELE-Aging Inspection6/10/20106/10/20106/10/2010 6:31:20 AM DONE
see doc expire
ELE08-01144 DOC - Permit Expired6/10/20106/10/20106/10/2010 6:31:07 AMAPASS
no activity
ELE08-01456 ELE-Aging Inspection6/10/20106/10/20106/10/2010 6:29:35 AM DONE
suc
ELE07-01929 ELE-Aging Inspection6/10/20106/10/20106/10/2010 6:28:51 AM DONE
see doc expire
ELE07-01929 DOC - Permit Expired6/10/20106/10/20106/10/2010 6:28:39 AMAPASS
no activity
ELE07-02270 ELE-Aging Inspection6/10/20106/10/20106/10/2010 6:27:25 AM DONE
see doc expire
ELE07-02270 DOC - Permit Expired6/10/20106/10/20106/10/2010 6:27:12 AMAPASS
no activity