BLD02-02994
| FIRE-Final Inspection | 6/10/2003 | 6/11/2003 | 6/11/2003 12:00:00 AM | A | FAIL |
|
|
DAN; Phone #: ###-#### Knox box has been installed but there is still no map for the facp and I need nfpa 72 record of completions 6/11/2003 1:06:52 PM
|
BLD03-00920
| FIRE-Final Inspection | 6/10/2003 | 6/11/2003 | 6/11/2003 12:00:00 AM | A | FAIL |
|
|
Provide exit signs and emergency lights as per plans. provide hazardous materials stickers as per plan. provide max occupancy sign per plan 6/11/2003 10:31:43 AM
|
FIR03-00116
| INSP-Final Inspection | 6/11/2003 | 6/11/2003 | 6/11/2003 12:00:00 AM | A | PASS |
|
|
Hood suppression system operated correctly. Signals went to the alarm panel and to central station.
|
BLD02-02435
| FIRE-Conference | 6/11/2003 | 6/11/2003 | 6/11/2003 12:00:00 AM | P | DONE |
|
|
oil storage tank venting, John ###-#### I met with John with Debest plumbing and telephone conference with sam. There are no code requirements found for venting of the oil storage tanks to the outside of the facility. I did refer the contractor to the UFC 7902 minimum requirements for venting of any storage tank. 6/11/2003 2:29:38 PM
|
FIR03-00254
| INSP-Sprinkler Rough-in/Hydro | 6/10/2003 | 6/11/2003 | 6/10/2003 10:43:17 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 6/10/2003 at 9:25:46 AM. Disp set to [CANC] by a contractor via Hello! on Jun 10 2003 10:43AM.
|