ELE07-01598
| Electrical Rough-In | 6/11/2007 | 6/11/2007 | 6/11/2007 3:33:44 PM | P | PART |
|
|
josh - 4th floor; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok anop
|
ELE07-02097
| Electrical Rough-In | 6/10/2007 | 6/11/2007 | 6/11/2007 2:08:21 PM | P | PASS |
|
|
Cover-inspection for heated floor in kitchen. Please call Adam @ ###-#### 1/2 hr. prior to inspection for access. Thank you! Phone #: ###-#### Internet Inspection Request from: Adam Staigle floor heat ok, also looked at fished in wiring. told elect contr no screws in plastic boxes neo violations retained he will correct them to meet code
|
ELE07-02098
| Electrical Rough-In | 6/11/2007 | 6/11/2007 | 6/11/2007 1:17:23 PM | P | CANC |
|
|
This work is at Slichter Architects. We wired 9 new ceiling lighting receptacles and 1 new wall switch and tied them into the old existing lighting circuit.Thanks!!! Dan. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called wrong address address needed is 6611 ustick and it is not in the system, also needs to calc out circuit fixtures added to Dan will follow up and reschedule
|
ELE07-00423
| Final | 6/11/2007 | 6/11/2007 | 6/11/2007 12:54:11 PM | P | FAIL |
|
|
daniel - pls call for access; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr. fee due called all corr. not made new violations created, 408.4 circuits be specific, 410.14(B) access for box MB closet, new violations island counter, 314.16 box fill, 300.14 free length short grd wires, 250.148 grd wiremold box
|
ELE07-01248
| Final | 6/7/2007 | 6/11/2007 | 6/11/2007 10:22:06 AM | A | PASS |
|
|
Per Jim S./Gene ###-#### - Journeyman Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
ELE07-01247
| Final | 6/7/2007 | 6/11/2007 | 6/11/2007 10:21:40 AM | A | PASS |
|
|
Per Jim S. Gene ###-####, Journeyman Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
ELE07-01249
| Final | 6/7/2007 | 6/11/2007 | 6/11/2007 10:21:17 AM | A | PASS |
|
|
Per Jim S./Gene ###-#### - journeyman Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
ELE07-01265
| Electrical Rough-In | 6/7/2007 | 6/11/2007 | 6/11/2007 8:52:51 AM | A | PASS |
|
|
Ground Inspection Please. Per Jim S. Gene ###-#### - Journeyman Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok for dirt cover
|
ELE07-01618
| Rough-In Permanent Service | 6/7/2007 | 6/11/2007 | 6/11/2007 8:52:14 AM | A | PASS |
|
|
Per Jim S./Gene ###-####-Journeyman Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i p/s u/g new ok
|