ELE07-02081
| Rough-In Permanent Service | 6/11/2007 | 6/11/2007 | 6/11/2007 3:41:10 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 6/11/2007 at 11:09:26 AM. Contact: ###-####. wrong type request, see ri
|
ELE07-02081
| Electrical Rough-In | 6/11/2007 | 6/11/2007 | 6/11/2007 3:34:44 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/11/2007 at 11:09:26 AM. Contact: ###-####. ok to pour gec, ric ok
|
ELE07-02100
| Conference | 6/11/2007 | 6/11/2007 | 6/11/2007 2:52:33 PM | P | DONE |
|
|
neil; Phone #: ###-#### Note: please call 1/2 hr prior Internet Inspection Request from: Cathy Chiles talked about service requirements for duplex that will convert to townhouse, told that they need 2 services and bld's and no penetration thru other side, or they can do duplex construction and change later, but not preferred method
|
ELE07-00920
| Final | 6/11/2007 | 6/11/2007 | 6/11/2007 2:07:44 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 210.52(E) sahll install recpt at rear of dwelling, 210.52(D) shall install recpt upper bath, 110.3 fan shall operate, lower bath, 422.11(A) overcurrent for a/c shall not exceed mfgrs marking
|
ELE07-00918
| Final | 6/11/2007 | 6/11/2007 | 6/11/2007 1:38:10 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 210.52(E) shall install recpt at rear of dwelling, 406.4 recpts shall be securely fastened, 406.5 recpt faceplates shall seat against mounting surface,406.4(D) recpt face shall be flush with or project from faceplate,422.11(A) overcurrent device for a/c shall not exceed mfgr marking on nameplate, 110.3 hall recpt shall operate
|
ELE07-00917
| Final | 6/11/2007 | 6/11/2007 | 6/11/2007 1:25:40 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 210.52(E) shall install recpt at rear of dwelling, 406.4 recpts shall be securely fastened in place, 406.4(D) recpt face shall be flush with or project from faceplate, 406.5 recpt faceplates shall completely cover opening and seat against mounting surface, 422.11(A) overcurrent device for a/c shall not exceed mfgrs marking
|
ELE07-02032
| Final | 6/6/2007 | 6/11/2007 | 6/11/2007 10:48:26 AM | A | PASS |
|
|
Inspection of existing house panel in garage for final. Re-fed existing 125A panel from new 200A service. Was not finished @ time of RI-Perm to reconnect ID Power. Home owner to be home 6/11/07 am. Thank you -- Lynn ###-####. Internet Inspection Request from: Lynn Solmon called to finish panel schedule as survey, ok to final
|
ELE07-02005
| Electrical Rough-In | 6/8/2007 | 6/11/2007 | 6/11/2007 10:13:13 AM | A | FAIL |
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 358.30(A) emt shall be supported within 12" of box, 330.30(B) mc cable shall be secured within 12" of box, and not over 6' in length without strapping,(whips) 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members, 300.11(A) support wires shall be provided for fixtures, BCC no violations shall be retained- no lv wiring on grid
|
ELE07-01846
| Final | 6/8/2007 | 6/11/2007 | 6/11/2007 9:23:03 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tina Payne ok to final, told contr to get lv off grid, signed occ card
|
ELE07-01246
| Final | 6/7/2007 | 6/11/2007 | 6/11/2007 8:24:34 AM | A | PASS |
|
|
Per Jim S. Gene - ###-#### journeyman Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final, signed card
|