Inspections for the day of: Monday, June 11, 2007.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00007 FIR-Aging Inspection6/11/20076/11/20076/13/2007 1:00:23 PM DONE
wip
FIR07-00463 INSP-Final Inspection6/11/20076/11/20076/11/2007 9:17:22 PMPPASS
Fire alarm work tested satisfactory, permit finaled.
FIR07-00179 INSP-Final Inspection6/11/20076/11/20076/11/2007 9:15:46 PMPPASS
Fire sprinkler passed final inspection, permit finaled.
FIR06-00985 INSP-Sprinkler Rough-in6/7/20076/11/20076/11/2007 9:14:32 PMPPART
Rough-in for building #2 is okay for cover, noted two areas where tenting needs to be adjusted-contractor to repair as agreed.
FIR06-00985 INSP-Sprinkler Rough-in/Hydro6/7/20076/11/20076/11/2007 2:52:41 PMPPART
AG hydrostatic test for building #2 passed.
FIR06-00602 INSP-Final Inspection6/7/20076/11/20076/11/2007 1:31:42 PMAPASS
All noted c/n items retested for verification of compliance, final building shell alarm testing completed satisfactory, need map at the panel as discussed and signage at the door to the FACP room to be verified at TI inspections.
BLD06-03197 FIRE-Final Inspection6/8/20076/11/20076/11/2007 1:28:31 PMAPART
Fire life safety is acceptable pending final of the project related fire sprinkler permit (need UG hydro and AG air tests).
FIR06-00504 INSP-Sprinkler Rough-in6/8/20076/11/20076/11/2007 1:25:53 PMAPART
OH rough-in for the dry system passed inspection, noted one missing seismic brace at the last piece of 3" main on the 1st floor, OH rough-in for the 3rd floor also completed including terraces, noted some wall changes within the suite spaces which will require some head spacing location mods.