FIR08-00361
| INSP-Sprinkler Rough-in | 6/10/2008 | 6/11/2008 | 6/11/2008 5:25:08 PM | P | PART |
|
|
Corrections listed at the previous inspection are finished, overhead rough-in is approved for cover.
|
BLD08-00673
| FIRE-Final Inspection | 6/11/2008 | 6/11/2008 | 6/11/2008 5:23:48 PM | P | PASS |
|
|
Shell permit fire life safety passed, prior to approval for tenant occupancy the building address discrepancy (1400 on the building vs. 1408 as indicated on the permit documents) is to be resolved.
|
FIR07-00830
| INSP-Alarm Testing | 6/10/2008 | 6/11/2008 | 6/11/2008 5:20:59 PM | A | PART |
|
|
See annotations on approved plan set for areas inspected and passed today including door holders, manual pull stations, SD's and HD's, noted areas not yet complete, one deleted SD, and overspaced smoke detectors at a common corridor.
|
BLD07-02583
| FIRE-Final Inspection | 6/10/2008 | 6/11/2008 | 6/11/2008 12:30:44 PM | A | PASS |
|
|
Correction notice items listed at the previous inspection verified for compliance, life safety finaled.
|
BLD08-00956
| FIRE-Conference | 6/10/2008 | 6/11/2008 | 6/11/2008 11:30:59 AM | A | DONE |
|
|
On site conference regarding exit signage at the new wall and exit door located in the basement level northeast side.
|
BLD08-00536
| FIRE-Final Inspection | 6/10/2008 | 6/11/2008 | 6/11/2008 10:53:17 AM | A | PASS |
|
|
Fire life safety final inspection passed, two minor adjustments made while on site including height AFF of the fire extinguisher.
|
BLD07-00855
| FIRE-Final Inspection | 6/10/2008 | 6/11/2008 | 6/11/2008 10:51:14 AM | A | FAIL |
|
|
Provide approved hardware at the north exit doors (all three), post signage at the main entry/exit doors, provide missing building address numbers on a contrasting backround as discussed, also reviewed tenant permit life safety items including EM lighting, exit signs, duct detectors, fire extinguishers, etc.
|