Inspections for the day of: Wednesday, June 11, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00361 INSP-Sprinkler Rough-in6/10/20086/11/20086/11/2008 5:25:08 PMPPART
Corrections listed at the previous inspection are finished, overhead rough-in is approved for cover.
BLD08-00673 FIRE-Final Inspection6/11/20086/11/20086/11/2008 5:23:48 PMPPASS
Shell permit fire life safety passed, prior to approval for tenant occupancy the building address discrepancy (1400 on the building vs. 1408 as indicated on the permit documents) is to be resolved.
FIR07-00830 INSP-Alarm Testing6/10/20086/11/20086/11/2008 5:20:59 PMAPART
See annotations on approved plan set for areas inspected and passed today including door holders, manual pull stations, SD's and HD's, noted areas not yet complete, one deleted SD, and overspaced smoke detectors at a common corridor.
BLD07-02583 FIRE-Final Inspection6/10/20086/11/20086/11/2008 12:30:44 PMAPASS
Correction notice items listed at the previous inspection verified for compliance, life safety finaled.
BLD08-00956 FIRE-Conference6/10/20086/11/20086/11/2008 11:30:59 AMADONE
On site conference regarding exit signage at the new wall and exit door located in the basement level northeast side.
BLD08-00536 FIRE-Final Inspection6/10/20086/11/20086/11/2008 10:53:17 AMAPASS
Fire life safety final inspection passed, two minor adjustments made while on site including height AFF of the fire extinguisher.
BLD07-00855 FIRE-Final Inspection6/10/20086/11/20086/11/2008 10:51:14 AMAFAIL
Provide approved hardware at the north exit doors (all three), post signage at the main entry/exit doors, provide missing building address numbers on a contrasting backround as discussed, also reviewed tenant permit life safety items including EM lighting, exit signs, duct detectors, fire extinguishers, etc.