Inspections for the day of: Thursday, June 11, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00382 INSP-Alarm Testing6/11/20096/11/20096/12/2009 9:01:07 AMPFAIL
Area in question is at the main entry lobby. Smoke detectors for door holder shutdown have been relocated from original installation and are not part of the submitted scope of work. No inspection performed. Spoke to contractor about what would be required for submitting the non-scope changed area. Also discussed requirement for submitting a plan modification for changes within the scope of work but are too extensive for field approval.
FIR09-00351 INSP-Final Inspection6/10/20096/11/20096/11/2009 3:36:15 PMPPASS
Permit finaled.
FIR08-00143 INSP-Final Inspection6/9/20096/11/20096/11/2009 3:14:02 PMPCANC
Scheduled by a contractor via Hello! on 6/9/2009 at 7:54:26 AM. Contact: ###-####.
FIR08-00818 INSP-Final Inspection6/9/20096/11/20096/11/2009 12:31:55 PMPFAIL
No testing was performed since a NetCom 5 or better was not available. I spoke to Stan Watts with AES and he stated that per UL a NetCom of 5 or better is required and this is backed up by the installation guide provided via email and forwarded to the fire alarm plan reviewer.
FIR08-00821 INSP-Final Inspection6/9/20096/11/20096/11/2009 12:31:42 PMPFAIL
No testing was performed since a NetCom 5 or better was not available. I spoke to Stan Watts with AES and he stated that per UL a NetCom of 5 or better is required and this is backed up by the installation guide provided via email and forwarded to the fire alarm plan reviewer.
FIR08-00822 INSP-Final Inspection6/9/20096/11/20096/11/2009 12:31:30 PMPFAIL
No testing was performed since a NetCom 5 or better was not available. I spoke to Stan Watts with AES and he stated that per UL a NetCom of 5 or better is required and this is backed up by the installation guide provided via email and forwarded to the fire alarm plan reviewer.
BLD07-01834 FIRE-Final Inspection6/10/20096/11/20096/11/2009 12:29:28 PMAFAIL
Need the project related fire alarm devices tested in the areas needing opened and the fire alarm contractor was not available nor was the inspection called in. I did a courtesy inspection and all appeared well but the city approved plans were not imediately available.
FIR07-01031 INSP-Sprinkler Rough-in6/10/20096/11/20096/11/2009 12:27:51 PMAPASS
The entry, side offices and activities room are ok for final. The dining area sprinkler piping has been covered prior to a rough-in inspection. The piping shall be exposed for inspection.