ELE09-00790
| ELE-Aging Inspection | 6/11/2010 | 6/11/2010 | 6/15/2010 3:50:36 PM | | CANC |
|
|
|
ELE09-00471
| ELE-Aging Inspection | 6/11/2010 | 6/11/2010 | 6/15/2010 3:49:58 PM | | CANC |
|
|
|
ELE09-02473
| ELE-Aging Inspection | 6/11/2010 | 6/11/2010 | 6/15/2010 3:49:49 PM | | CANC |
|
|
|
ELE10-00805
| Electrical Rough-In | 6/11/2010 | 6/11/2010 | 6/11/2010 4:05:58 PM | P | PASS |
|
|
Cal- call for access Phone #: ###-####
|
ELE10-00805
| Final | 6/11/2010 | 6/11/2010 | 6/11/2010 4:05:49 PM | P | PASS |
|
|
Cal- call for access Phone #: ###-####
|
ELE10-00625
| Rough-In Permanent Service | 6/11/2010 | 6/11/2010 | 6/11/2010 4:05:23 PM | P | FAIL |
|
|
Jamie''s cell is ###-#### Inspection requested from web by: Jamie Winters called stillneeds to terminate GEC at neutral (grounded) bus, not the equipment grounding bus
|
ELE10-00915
| Electrical Rough-In | 6/11/2010 | 6/11/2010 | 6/11/2010 4:03:05 PM | P | PASS |
|
|
Corey Phone #: ###-#### ceilings
|
ELE10-00882
| Final | 6/11/2010 | 6/11/2010 | 6/11/2010 4:02:28 PM | P | PASS |
|
|
Inspection requested from web by: Tracy Robertson Phone #: ###-####
|
ELE09-01933
| Final | 6/10/2010 | 6/11/2010 | 6/11/2010 4:02:00 PM | P | PASS |
|
|
Inspection requested from web by: Terry Scott Phone #: ###-####
|
ELE10-00739
| Final | 6/11/2010 | 6/11/2010 | 6/11/2010 4:01:12 PM | P | PASS |
|
|
danny Phone #: ###-#### ok card signed
|
ELE09-00550
| Final | 6/10/2010 | 6/11/2010 | 6/11/2010 4:00:34 PM | A | PASS |
|
|
Please do a final inspection on the rearranged kitchen. Lighting, outlets, dishwasher, water heater etc. The Church will be occupied between 9:00am and 4:30pm. Sorry for the delay, only received permission to finish the dishwasher last week. Inspection requested from web by: nathan palmer Phone #: ###-####ok survey posted called
|
ELE10-00824
| Permanent Service | 6/11/2010 | 6/11/2010 | 6/11/2010 12:59:30 PM | A | FAIL |
|
|
Inspection requested from web by: david bradshaw Phone #: ###-#### needs bond screw or strap equip grd bus, also bushing
|
ELE10-00878
| Final | 6/11/2010 | 6/11/2010 | 6/11/2010 11:41:20 AM | P | PASS |
|
|
Jared-Please call at least 30 mins prior for access Phone #: ###-####
|
ELE09-01932
| Final | 6/10/2010 | 6/11/2010 | 6/11/2010 10:25:59 AM | A | PART |
|
|
Final for phase 10 only. Please don''t final permit. Nick is the contact his no. is ###-#### ok
|
ELE10-01273
| Final | 6/10/2010 | 6/11/2010 | 6/11/2010 10:25:03 AM | A | PASS |
|
|
Contact: John Ostolasa Inspection requested from web by: Deb Gooden Phone #: ###-####
|
ELE10-01101
| Electrical Rough-In | 6/10/2010 | 6/11/2010 | 6/11/2010 9:15:04 AM | A | FAIL |
|
|
WIRES MOVED FOR DOORWAY Inspection requested from web by: Aaron Decker Phone #: ###-#### called stap all cables and raceways, nail plates and 11/4" , needs required sign circuit
|
ELE10-00739
| Final | 6/10/2010 | 6/11/2010 | 6/11/2010 8:34:59 AM | A | CANC |
|
|
grid and final insp//Danny Phone #: ###-#### nr see added r/i
|
ELE10-00739
| Electrical Rough-In | 6/11/2010 | 6/11/2010 | 6/11/2010 8:34:41 AM | A | PART |
|
|
grid and final insp//Danny Phone #: ###-#### needs to strap cables, seperate cables, and wires for boxes
|
ELE09-02028
| Final | 6/11/2010 | 6/11/2010 | 6/11/2010 7:10:48 AM | A | PASS |
|
|
|
ELE09-00660
| Final | 6/11/2010 | 6/11/2010 | 6/11/2010 7:09:46 AM | A | PASS |
|
|
|
ELE09-01745
| Final | 6/11/2010 | 6/11/2010 | 6/11/2010 7:09:04 AM | A | PASS |
|
|
work was done on permit #ele09-02033
|
ELE10-01245
| Final | 6/10/2010 | 6/11/2010 | 6/10/2010 1:46:08 PM | A | PASS |
|
|
Please inspect Bench has been removed and the Grounding is complete. Mark is our contact ###-#### Inspection requested from web by: Clint Tate Phone #: ###-####
|