FIR07-00371
| FIR-Aging Inspection | 6/11/2010 | 6/11/2010 | 6/16/2010 1:33:13 PM | | DONE |
|
|
Site visit confirmed construction on this project has been suspended.
|
FIR10-00233
| INSP-Final Inspection | 6/10/2010 | 6/11/2010 | 6/16/2010 12:51:13 PM | P | FAIL |
|
|
One notification appliance failed to operate, noted mag locks at the NE exit door do not release on fire alarm. Duct detectors tested satisfactory.
|
FIR10-00240
| INSP-Final Inspection | 6/11/2010 | 6/11/2010 | 6/11/2010 3:44:43 PM | P | PASS |
|
|
Scope of work passed functional testing. Permit finaled.
|
FIR06-00474
| DOC - Permit Expired | 6/11/2010 | 6/11/2010 | 6/11/2010 3:42:51 PM | P | PASS |
|
|
Tenant has relocated, building is vacant. Permit expired- IFC 2006 sec. 105.3.1
|
FIR03-00297
| DOC - Permit Expired | 6/11/2010 | 6/11/2010 | 6/11/2010 3:38:13 PM | P | PASS |
|
|
Ref IFC 2006 sec. 105.3.1
|
FIR03-00297
| FIR-Aging Inspection | 6/11/2010 | 6/11/2010 | 6/11/2010 3:36:58 PM | | DONE |
|
|
|
FIR06-00336
| DOC - Permit Finaled | 6/11/2010 | 6/11/2010 | 6/11/2010 3:31:43 PM | P | PASS |
|
|
Tested in conjunction with FIR06-00527.
|
FIR06-00336
| FIR-Aging Inspection | 6/11/2010 | 6/11/2010 | 6/11/2010 3:30:40 PM | | DONE |
|
|
|
BLD10-00257
| FIRE-Final Inspection | 6/11/2010 | 6/11/2010 | 6/11/2010 3:21:23 PM | P | PASS |
|
|
Reinspection passed for noted correction items. Comments # 10 and 11 on the fire code review are not applicable- building is not equipped with a fire alarm system. HVAC units are below min. cfm to require duct detectors.
|
BLD08-00264
| FIRE-Final Inspection | 6/10/2010 | 6/11/2010 | 6/11/2010 3:17:51 PM | A | FAIL |
|
|
Door hardware at the new F1 area needs to operate "fail safe" in the direction of travel, fire lane marking is not finished, discussed lock at gate, schedule for project completion.
|
BLD10-00257
| FIRE-Final Inspection | 6/10/2010 | 6/11/2010 | 6/11/2010 3:12:47 PM | A | FAIL |
|
|
Missing building address numbers per review note #2, one exit sign per plan review red-lines needs to be relocated. EM lighting passed.
|