FIR12-00186
| INSP-Sprinkler Rough-in | 6/11/2012 | 6/11/2012 | 6/12/2012 8:24:08 AM | P | PART |
|
|
Overhead rough-in inspection completed. Noted obstruction at ductwork >4' one location, exposed wood at the pharmacy accordian door pocket to be protected or verified for min. combustibility. Coverage at the men's restroom to be adjusted due to light fixture obstruction, FDC and dry pendent heads in the coolers are not yet installed.
|
BLD12-00928
| FIRE-Final Inspection | 6/8/2012 | 6/11/2012 | 6/12/2012 7:56:28 AM | P | PASS |
|
|
Fire life safety approved pending one PFE is provided at the mezzanine level and signage regarding max. floor load psf is posted per stamped plan annotations.
|
BLD12-01271
| FIRE-Final Inspection | 6/11/2012 | 6/11/2012 | 6/12/2012 7:52:59 AM | P | PASS |
|
|
Fire life safety inspection passed. Revised floorplan to be provided as discussed.
|
FIR12-00268
| INSP-Final Inspection | 6/11/2012 | 6/11/2012 | 6/12/2012 7:51:32 AM | P | PASS |
|
|
Fire alarm permit final approved. Missing record of completion on site- contractor to provide as agreed.
|
FIR12-00268
| INSP-Alarm Testing | 6/8/2012 | 6/11/2012 | 6/12/2012 7:49:49 AM | P | PASS |
|
|
Fire alarm work passed functional testing.
|
BLD12-01434
| FIRE-Final Inspection | 6/8/2012 | 6/11/2012 | 6/11/2012 12:58:42 PM | A | FAIL |
|
|
Post one fire extinguisher at each floor level, provide approved hardware at the main entry/exit door as discussed.
|
BLD12-01300
| FIRE-Final Inspection | 6/8/2012 | 6/11/2012 | 6/11/2012 12:56:44 PM | A | FAIL |
|
|
Several correction items noted including exit hardware issues, address and signage items, overspaced fire sprinkler coverage, incorrect door swing, unprotected openings in the 2 hour rated wall, racking permit required, etc. No corrections listed for the north building.
|
BLD12-01320
| FIRE-Final Inspection | 6/11/2012 | 6/11/2012 | 6/11/2012 12:00:00 AM | P | CANC |
|
|
yotham Phone #: ###-####
|