BLD11-01267
| FIRE-Alarm Testing | 6/11/2012 | 6/11/2012 | 6/12/2012 7:32:54 AM | P | DONE |
|
|
Todays inspection I walked through areas A and B, all of the second floor and the west half of the first floor. I tested the residential smoke alarms in these areas.
|
FIR12-00161
| INSP-Final Inspection | 6/11/2012 | 6/11/2012 | 6/12/2012 7:31:41 AM | P | FAIL |
|
|
Todays inspection I walked through areas A and B, all of the second floor and the west half of the first floor. I found many rooms where the sprinkler heads are covered due to touch up work by painters. I gave a list of room numbers with the covered heads to the job superintendant.
|
FIR11-00662
| INSP-Alarm Testing | 6/11/2012 | 6/11/2012 | 6/11/2012 3:57:59 PM | P | DONE |
|
|
Todays testing was for the first and second floor fire door smoke detectors in the west wing (area A). Both relays had to be replaced while I waited. The relay was also replaced at the smoke detector/smoke damper at the first floor, west elevator. The programing needs changes so that upon alarm silence the dampers do not open. Could not test the elevators since the reset key was not available.
|
BLD12-00248
| FIRE-Final Inspection | 6/11/2012 | 6/11/2012 | 6/11/2012 1:57:24 PM | P | FAIL |
|
|
Mount the fire extinguishers as discussed. Repair the interior emergency lights. Repair the south exterior exit discharge light.
|
FIR12-00227
| INSP-Final Inspection | 6/11/2012 | 6/11/2012 | 6/11/2012 1:56:42 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00219
| INSP-Final Inspection | 6/8/2012 | 6/11/2012 | 6/11/2012 1:55:44 PM | A | PASS |
|
|
Permit finaled
|