Inspections for the day of: Tuesday, June 11, 2013.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00534 ELE-Aging Inspection6/11/20136/11/20136/11/2013 3:42:39 PM DONE
still under construction
ELE11-01137 ELE-Aging Inspection6/11/20136/11/20136/11/2013 3:37:08 PM DONE
still waiting on owner
ELE12-00538 ELE-Aging Inspection6/11/20136/11/20136/11/2013 3:23:55 PM DONE
Contractor to call for final
ELE13-00799 Final6/11/20136/11/20136/11/2013 3:16:54 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson
210.12(B)- All 15 and 20 amp branch circuits serviving bedroom shall be protected by a AFCI device. Master bed outlet.
Up closet light not hung.
Up closet switch shall have cover.
Kitchen GFCI circuit not working.
ELE13-00418 Electrical Rough-In6/11/20136/11/20136/11/2013 2:58:48 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton
As noted on print wall rough in ok cover
ELE13-01467 Electrical Rough-In6/11/20136/11/20136/11/2013 1:35:21 PMPPASS
underground-Max--zoo at gate 4 Phone #: ###-#### Underground and concrete encased rough in ok cover
ELE13-01454 Permanent Service6/10/20136/11/20136/11/2013 12:51:37 PMAPASS
Late am if at all possible. Thank you Phone #: ###-#### >> Inspection requested via web by Dan Wright p/s u/g n ok
ELE13-01039 Final6/11/20136/11/20136/11/2013 12:39:41 PMPPASS
Lock box 0266 Phone #: ###-#### >> Inspection requested via web by George Lloyd
Final ok
ELE13-01219 Final6/10/20136/11/20136/11/2013 10:37:24 AMANR
Phone #: ###-#### >> Inspection requested via web by Dan Surerus
Microwave receptical not trimmed out or labeled
ELE13-01466 Final6/11/20136/11/20136/11/2013 10:19:52 AMPPASS
This site is at the northwest corner of the building at the alley.
Thanks !!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
Final ok
ELE13-01466 Rough-In Permanent Service6/11/20136/11/20136/11/2013 10:08:01 AMPPASS
This site is at the northwest corner of the building at the alley.
Thanks !!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
rough in ok p/s u/g n ok
ELE13-01463 Temporary Service6/11/20136/11/20136/11/2013 10:03:02 AMAFAIL
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn
Loose ground in panel
Replace broken 50 amp receptical
ELE13-01468 Final6/11/20136/11/20136/11/2013 9:45:45 AMPPASS
This site is at the corner of the property in the corner of Crestline x Claremont, next to the power company pad mount transformer.
Thanks !!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
Final ok
ELE13-01468 Rough-In Permanent Service6/11/20136/11/20136/11/2013 9:43:35 AMPPASS
This site is at the corner of the property in the corner of Crestline x Claremont, next to the power company pad mount transformer.
Thanks !!! Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell
Rough in ok cover p/s u/g n ok
ELE13-01276 Rough-In Permanent Service6/10/20136/11/20136/11/2013 9:15:56 AMAPASS
Mucho Phone #: ###-#### Rough in ok cover
p/s u/g n ok
ELE13-01134 Final6/11/20136/11/20136/11/2013 8:48:49 AMAPASS
Please call 1/2 hour before going to site. Phone #: ###-#### >> Inspection requested via web by PAUL PINNEY Final ok
ELE12-00520 ELE-Aging Inspection6/11/20136/11/20136/11/2013 8:43:23 AM DONE
Met contractor at job and finalled
ELE12-00520 Final6/11/20136/11/20136/11/2013 8:41:18 AMPPASS
Kitchen remodel final ok
ELE13-01088 Final6/10/20136/11/20136/11/2013 8:34:04 AMAFAIL
The access code is 5555, thx. Phone #: ###-#### >> Inspection requested via web by Stephen Kren GFCI right of range defective