Inspections for the day of: Thursday, June 11, 2015.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01609 Electrical Rough-In6/10/20156/11/20156/11/2015 10:59:02 AMAFAIL
IN wall rough in - office area. please call Lance if questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott NEC 330.30(B) MC shall be secured wthin 12 in. of every box, cabnet. NEC 358.30(A) EMT shall be secured wthin 3 ft. of each outlet box, cabnet
ELE15-01451 Final6/10/20156/11/20156/11/2015 10:28:13 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot final ok
ELE15-01170 Electrical Rough-In6/10/20156/11/20156/11/2015 9:39:16 AMAPASS
Justin Hamby-Install Foreman Phone #: ###-#### Inspection requested via web by Laurie Hoelscher UL listed Jimmy John's signs rough-in ok
ELE15-00292 Final6/10/20156/11/20156/11/2015 9:21:43 AMAPASS
Robert Phone #: ###-#### final ok
ELE15-00292 Electrical Rough-In6/11/20156/11/20156/11/2015 9:21:22 AMAPASS
Robert Phone #: ###-#### rough-in ok