Inspections for the day of: Monday, June 11, 2018.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01998 Electrical Rough-In6/11/20186/11/20186/11/2018 2:48:01 PMPPASS
Please call Tyler Reed (###-####) for specifics. Phone #: ###-#### Inspection requested via web by Scott Campbell
Concrete encased up to bond steel beam and into 3 gang mason box to tie in rough in ok cover
ELE17-01337 Electrical Rough-In6/8/20186/11/20186/11/2018 2:46:24 PMAPART
All drop ceilings 1st floor except kitchen - rough
Roof - final
2nd Floor - Partial final Phone #: ###-#### Inspection requested via web by Clint Tate
Guest laundry flexible cords above grid. Work areas 2 rms, laundry areas, meeting rm, managers offices, fitness rm, ice rm grid rough in ok cover
Roof- M-3 35, 37 25 amp max, 34, 36 55 amp max, 38, 40 25 amp max
M-1 20, 22, 24 50 amp max.
Level 2- 212, 214, 218, 222, 224, 228 NR, 217 switched power
ELE18-01573 Electrical Rough-In6/11/20186/11/20186/11/2018 9:12:56 AMAFAIL
Ceiling cover. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
300.15- MC cable shall terminate in a box. 1 area behind reception 1 in office out of wall.
300.11- MC and other cable shall be supported insependant of grid. Fixture whip and low volt.