Inspections for the day of: Thursday, June 11, 2020.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00602 Final6/10/20206/11/20206/12/2020 9:34:37 AMPFAIL
Homeowner is Sean Burdick. His cell phone is ###-#### Phone #: ###-#### Inspection requested via web by Deslie Duskin 210.8(A)- All 15 and 20 amp 120 volt receptacle outlets installed with in 6' of a sink shall have GFCI protection. Basement mech. area. 314.25- All boxes shall have covers. Kitchen old switch location,sump pump, jetted tub receptacles, transformer in basement ceiling. 422.30- A disconnecting means shall be provided for central air furnace in basement. Owner provided info on all work completed.
ELE20-01997 Electrical Rough-In6/11/20206/11/20206/11/2020 3:08:34 PMPPASS
Contact is Jim Noll Phone #: ###-#### Inspection requested via web by Scott Campbell Service receptacle outlets shall be installed at same level and with in 25' of units mounted above parking garage ramp as per 210.63. North elevator yet to complete, South elevator equipment replacement complete. rough in ok.
ELE20-01869 Electrical Rough-In6/11/20206/11/20206/11/2020 1:20:07 PMPPASS
Walls inspection
Lockbox on fire extinguisher box in hallway. Code 5433 Phone #: ###-#### Inspection requested via web by Dean Gernaat Relocated wall rough in ok cover.
ELE20-00894 Final6/10/20206/11/20206/11/2020 11:59:05 AMAFAIL
Call me when you are there and I’ll give you the lock box code if no one is home, thank you. Kitchen remodel Phone #: ###-#### Inspection requested via web by Keith Chetta
210.8(A)- All receptacle outlets serving counter top areas shall have GFCI protection. Left of refer and right of sink.
406.12- All receptacle outlets in kittchen remodel area shall be tamper resistant type. Left of refer.
ELE20-00121 Final6/10/20206/11/20206/11/2020 11:25:41 AMAFAIL
Bill *screened* Phone #: ###-####
110.3- Down patio switches not working as per instructions. 1 locks out rest. 210.12- All bedroom outlets shall have AFCI protection. Down switch for patio lights, master bed entry. 210.52(C)- Pantry counter top areas shall have receptacle outets installed so that no point on counter is more than 24" from a receptacle outlet. 408.4- Complete circuit directory- unable to locate 130 RV receptacle in garage, Light over tub blanked off.
ELE20-01918 Temporary Service6/10/20206/11/20206/11/2020 10:16:46 AMAFAIL
Please feel free to contact Kaiden ###-#### with questions. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.12(B)- Electrical equpment shall not be damaged. 250 GFCI breaker broke in half.
ELE20-01853 Electrical Rough-In6/10/20206/11/20206/11/2020 9:56:09 AMAPASS
Electrical rough-in inspection please. Have a bless day! Phone #: ###-#### Inspection requested via web by Kyle Lott City approved set of prints
Wall rough in ok cover
ELE20-01989 Permanent Service6/10/20206/11/20206/11/2020 9:30:08 AMAPASS
Ready for IPCO to pull meter out of old service panel and energize new, they will not do until new transformer is set. we will coordinate same day to replace interior garage panel and separate neutrals and grounds. then call in for final. dryer and range are 4 wire, water is Poly, rods are driven. Thank You Phone #: ###-#### Inspection requested via web by Steve Blackmer p/s u/g n ok
ELE20-01990 Electrical Rough-In6/10/20206/11/20206/11/2020 9:08:59 AMAFAIL
please call at time of inspection Phone #: ###-#### Inspection requested via web by Ryan Wake City approved set of prints confirmed in break room.
517.13- All outlets in patient care spaces shall be wired in a medical grade wiring method. South and north treatment rooms and confirm wirint method of existing outlets in treatment areas.
ELE20-01540 Final6/10/20206/11/20206/10/2020 12:32:43 PMAPASS
Please call Taber Phone #: ###-#### Inspection requested via web by Kevin Perez Missed call in cut off, I was able to squeeze inspection in 6-10-20 pm. Final ok