ELE01-00122
| ELE-Aging Inspection | 6/12/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | | PASS |
|
|
no action. 6/12/2001 3:30:05 PM
|
ELE01-01677
| Final | 6/11/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 06/11/2001 at 09:25:50. Contact: ###-####. completed. 6/12/2001 8:56:19 AM
|
ELE01-01678
| Final | 6/11/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 06/11/2001 at 09:26:34. Contact: ###-####. completed 6/12/2001 8:56:46 AM
|
ELE01-01727
| Electrical Rough-In | 6/11/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 06/11/2001 at 09:55:12. Contact: ###-####. ground level; radiology doctor offices 6/12/2001 9:33:39 AM 6/12/2001 9:33:43 AM
|
ELE01-00851
| Electrical Rough-In | 6/11/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | A | PART |
|
|
shane ###-####. ground-level decking; ele r/i ok. 6/12/2001 9:57:28 AM
|
ELE00-04373
| Final | 6/11/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 06/11/2001 at 16:26:11. Contact: ###-####. nec: 110-16. clearances; shall have 36 inches in front of disconnect, (rooftop hvac unit). nec: 210-8. rooftop hvac units shall have gfci recepticles, ( not operational). 6/12/2001 11:19:42 AM
|
ELE01-01836
| Electrical Rough-In | 6/12/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | P | PART |
|
|
###-####. perm/svc, connection for power only. ok.
p/s oh r advanced ele #1836
called in to Patty for connection to power. 6/12/2001 3:23:56 PM
|
ELE01-01916
| Final | 6/12/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | P | PART |
|
|
###-#### Dan. conference; roof-top swamp coolers (2) branch circuits. 6/12/2001 4:36:47 PM
|
ELE01-01762
| Electrical Rough-In | 6/12/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | P | PASS |
|
|
upstairs Mike ###-####. upstairs r/i, ok. corrections completed. 6/12/2001 2:18:52 PM
|
ELE01-01676
| Final | 6/12/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 06/12/2001 at 09:32:05. Contact: ###-####.
|
ELE01-01177
| Electrical Rough-In | 6/11/2001 | 6/12/2001 | 6/12/2001 12:00:00 AM | P | PART |
|
|
kitchen, 2-bathrooms r/i. ok 6/12/2001 12:00:16 PM
|
ELE00-02999
| Electrical Rough-In | 6/11/2001 | 6/12/2001 | 6/11/2001 12:00:00 AM | A | PASS |
|
|
###-#### not done yet
|