Inspections for the day of: Thursday, June 12, 2003.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-01709 Electrical Rough-In6/11/20036/12/20036/12/2003 12:00:00 AMAFAIL
###-#### kevin called needs clean 20 amp circuit to feed bath rm recepts only, and 410.8 clearence closet light fixture 6/12/2003 11:44:23 AM
ELE03-01494 Final6/11/20036/12/20036/12/2003 12:00:00 AMAPASS
don ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 6/12/2003 9:27:34 AM
ELE03-01496 Final6/11/20036/12/20036/12/2003 12:00:00 AMAPASS
don ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 6/12/2003 9:27:50 AM
ELE03-00808 Final6/11/20036/12/20036/12/2003 12:00:00 AMANH
Scheduled by a contractor via Hello! on 6/11/2003 at 3:11:15 PM. Contact: ###-####. no access called 6/12/2003 10:49:29 AM
ELE03-01713 Temporary Service6/11/20036/12/20036/12/2003 12:00:00 AMAFAIL
###-#### cor. and fee due posted called 527.6 (B) gfci for 220 volt 406.8 (B) needs in use cover, 110.12(C) clean t/s 6/12/2003 9:58:33 AM
ELE02-03818 Final6/11/20036/12/20036/12/2003 12:00:00 AMAPART
ok to cover--jim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie patio bar r/i ok 6/12/2003 11:04:19 AM
ELE03-01312 Final6/12/20036/12/20036/12/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 6/12/2003 at 7:06:12 AM. Contact: ###-####. cor. posted called grd to new p/s to water system, isolate grd and neutrals at sub panel also needs insulated neutral needs recept and light for heating equip 6/12/2003 12:16:23 PM
ELE03-00281 Electrical Rough-In6/12/20036/12/20036/12/2003 12:00:00 AMPFAIL
ricks electric underground pipe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see pm# ele03-00312 6/12/2003 2:37:42 PM
ELE03-00312 Electrical Rough-In6/12/20036/12/20036/12/2003 12:00:00 AMPFAIL
ricks electric underground pipe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 300.5 needs proper depth for u/g 18 inches and 24 for road and parking lot called 6/12/2003 2:38:31 PM
ELE03-00521 Electrical Rough-In6/12/20036/12/20036/12/2003 12:00:00 AMPFAIL
ricks electric underground pipe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see pm#ele03-00312 6/12/2003 2:38:16 PM
ELE03-00808 Final6/12/20036/12/20036/12/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 6/12/2003 at 9:54:38 AM. Contact: ###-####. ok 6/12/2003 3:12:15 PM
ELE03-01701 Temporary Service6/12/20036/12/20036/12/2003 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas
t/s u/g new ok 6/12/2003 12:58:56 PM
ELE01-03617 Final6/12/20036/12/20036/12/2003 12:00:00 AMPPART
01 with Lea
ELE03-01192 Final6/11/20036/12/20036/12/2003 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok 6/12/2003 1:46:26 PM