ELE03-01709
| Electrical Rough-In | 6/11/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | A | FAIL |
|
|
###-#### kevin called needs clean 20 amp circuit to feed bath rm recepts only, and 410.8 clearence closet light fixture 6/12/2003 11:44:23 AM
|
ELE03-01494
| Final | 6/11/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | A | PASS |
|
|
don ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 6/12/2003 9:27:34 AM
|
ELE03-01496
| Final | 6/11/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | A | PASS |
|
|
don ; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 6/12/2003 9:27:50 AM
|
ELE03-00808
| Final | 6/11/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | A | NH |
|
|
Scheduled by a contractor via Hello! on 6/11/2003 at 3:11:15 PM. Contact: ###-####. no access called 6/12/2003 10:49:29 AM
|
ELE03-01713
| Temporary Service | 6/11/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | A | FAIL |
|
|
###-#### cor. and fee due posted called 527.6 (B) gfci for 220 volt 406.8 (B) needs in use cover, 110.12(C) clean t/s 6/12/2003 9:58:33 AM
|
ELE02-03818
| Final | 6/11/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | A | PART |
|
|
ok to cover--jim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie patio bar r/i ok 6/12/2003 11:04:19 AM
|
ELE03-01312
| Final | 6/12/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/12/2003 at 7:06:12 AM. Contact: ###-####. cor. posted called grd to new p/s to water system, isolate grd and neutrals at sub panel also needs insulated neutral needs recept and light for heating equip 6/12/2003 12:16:23 PM
|
ELE03-00281
| Electrical Rough-In | 6/12/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | P | FAIL |
|
|
ricks electric underground pipe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see pm# ele03-00312 6/12/2003 2:37:42 PM
|
ELE03-00312
| Electrical Rough-In | 6/12/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | P | FAIL |
|
|
ricks electric underground pipe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 300.5 needs proper depth for u/g 18 inches and 24 for road and parking lot called 6/12/2003 2:38:31 PM
|
ELE03-00521
| Electrical Rough-In | 6/12/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | P | FAIL |
|
|
ricks electric underground pipe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see pm#ele03-00312 6/12/2003 2:38:16 PM
|
ELE03-00808
| Final | 6/12/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/12/2003 at 9:54:38 AM. Contact: ###-####. ok 6/12/2003 3:12:15 PM
|
ELE03-01701
| Temporary Service | 6/12/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas
t/s u/g new ok 6/12/2003 12:58:56 PM
|
ELE01-03617
| Final | 6/12/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | P | PART |
|
|
01 with Lea
|
ELE03-01192
| Final | 6/11/2003 | 6/12/2003 | 6/12/2003 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok 6/12/2003 1:46:26 PM
|