Inspections for the day of: Monday, June 12, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02148 Electrical Rough-In6/12/20066/12/20066/12/2006 4:39:50 PMPPART
###-#### - mitch Note: ufier and underground ok electrode ok for concrete cover only
ELE06-00305 Final6/12/20066/12/20066/12/2006 4:18:47 PMPFAIL
Scheduled by a contractor via Hello! on 6/12/2006 at 10:27:34 AM. Contact: ###-####. corr 410.8(A&D) clearence fixture front entry closet also wires between ceiling and fixture, 408.4 panel schedule shall be specific as to purpose
ELE06-01698 Electrical Rough-In6/12/20066/12/20066/12/2006 3:45:49 PMPPART
ceiling cover...; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok needs too secure cable support wires from structure too grid
ELE06-01930 Permanent Service6/12/20066/12/20066/12/2006 3:22:35 PMPPASS
bill - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
p/s o/h new ok
ELE06-02143 Final6/12/20066/12/20066/12/2006 2:44:15 PMPPASS
rod; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-02131 Electrical Rough-In6/12/20066/12/20066/12/2006 2:15:02 PMPFAIL
Re-inspection of conduit/trench Contact Bob,; Phone #: ###-#### Internet Inspection Request from: Julie Schroder
corr. talked with contractor 300.5 Table pvc shall be 18" for depth
ELE06-02144 Rough-In Permanent Service6/12/20066/12/20066/12/2006 1:42:34 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dan Rohl r/i p/s u/g new ok
ELE06-01985 Rough-In Permanent Service6/12/20066/12/20066/12/2006 1:09:04 PMPFAIL
Scheduled by a contractor via Hello! on 6/12/2006 at 9:56:55 AM. Contact: ###-####. called corrections not made still needs 11/4"
ELE06-02023 Electrical Rough-In6/12/20066/12/20066/12/2006 1:06:56 PMPFAIL
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles not ready corrections not made
ELE06-02131 Electrical Rough-In6/9/20066/12/20066/12/2006 10:21:47 AMAFAIL
CALL BOB W/QUESTIONS : INSPECT CONDUIT/TRENCH ONLY. ; Phone #: ###-#### Internet Inspection Request from: Julie Schroder trench covered before inspection called contractor will uncover and call for reinspection
ELE06-00772 Final6/9/20066/12/20066/12/2006 9:59:27 AMAPASS
code=1000; Phone #: ###-#### Internet Inspection Request from: William Zerfas ok
ELE06-02069 Conference6/10/20066/12/20066/12/2006 9:19:28 AMADONE
Scheduled by a contractor via Hello! on 6/10/2006 at 8:18:19 AM. Contact: ###-####. conference about xformers at fish tank area
ELE06-02069 Electrical Rough-In6/12/20066/12/20066/12/2006 9:18:19 AMAPART
Scheduled by a contractor via Hello! on 6/10/2006 at 8:18:19 AM. Contact: ###-####. r/i for soffit around mountain
ELE06-01982 Final6/11/20066/12/20066/12/2006 8:38:29 AMAPASS
Scheduled by a contractor via Hello! on 6/11/2006 at 8:46:44 PM. Contact: ###-####.
ELE06-01982 Electrical Rough-In6/12/20066/12/20066/12/2006 8:38:15 AMAPASS
Scheduled by a contractor via Hello! on 6/11/2006 at 8:46:44 PM. Contact: ###-####. survey posted label panel bond hot and cold pipe, shall not ID 6 or smaller neutral, derate or remove conductors from conduit