ELE06-02148
| Electrical Rough-In | 6/12/2006 | 6/12/2006 | 6/12/2006 4:39:50 PM | P | PART |
|
|
###-#### - mitch Note: ufier and underground ok electrode ok for concrete cover only
|
ELE06-00305
| Final | 6/12/2006 | 6/12/2006 | 6/12/2006 4:18:47 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/12/2006 at 10:27:34 AM. Contact: ###-####. corr 410.8(A&D) clearence fixture front entry closet also wires between ceiling and fixture, 408.4 panel schedule shall be specific as to purpose
|
ELE06-01698
| Electrical Rough-In | 6/12/2006 | 6/12/2006 | 6/12/2006 3:45:49 PM | P | PART |
|
|
ceiling cover...; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok needs too secure cable support wires from structure too grid
|
ELE06-01930
| Permanent Service | 6/12/2006 | 6/12/2006 | 6/12/2006 3:22:35 PM | P | PASS |
|
|
bill - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s o/h new ok
|
ELE06-02143
| Final | 6/12/2006 | 6/12/2006 | 6/12/2006 2:44:15 PM | P | PASS |
|
|
rod; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
|
ELE06-02131
| Electrical Rough-In | 6/12/2006 | 6/12/2006 | 6/12/2006 2:15:02 PM | P | FAIL |
|
|
Re-inspection of conduit/trench Contact Bob,; Phone #: ###-#### Internet Inspection Request from: Julie Schroder corr. talked with contractor 300.5 Table pvc shall be 18" for depth
|
ELE06-02144
| Rough-In Permanent Service | 6/12/2006 | 6/12/2006 | 6/12/2006 1:42:34 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl r/i p/s u/g new ok
|
ELE06-01985
| Rough-In Permanent Service | 6/12/2006 | 6/12/2006 | 6/12/2006 1:09:04 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/12/2006 at 9:56:55 AM. Contact: ###-####. called corrections not made still needs 11/4"
|
ELE06-02023
| Electrical Rough-In | 6/12/2006 | 6/12/2006 | 6/12/2006 1:06:56 PM | P | FAIL |
|
|
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles not ready corrections not made
|
ELE06-02131
| Electrical Rough-In | 6/9/2006 | 6/12/2006 | 6/12/2006 10:21:47 AM | A | FAIL |
|
|
CALL BOB W/QUESTIONS : INSPECT CONDUIT/TRENCH ONLY. ; Phone #: ###-#### Internet Inspection Request from: Julie Schroder trench covered before inspection called contractor will uncover and call for reinspection
|
ELE06-00772
| Final | 6/9/2006 | 6/12/2006 | 6/12/2006 9:59:27 AM | A | PASS |
|
|
code=1000; Phone #: ###-#### Internet Inspection Request from: William Zerfas ok
|
ELE06-02069
| Conference | 6/10/2006 | 6/12/2006 | 6/12/2006 9:19:28 AM | A | DONE |
|
|
Scheduled by a contractor via Hello! on 6/10/2006 at 8:18:19 AM. Contact: ###-####. conference about xformers at fish tank area
|
ELE06-02069
| Electrical Rough-In | 6/12/2006 | 6/12/2006 | 6/12/2006 9:18:19 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 6/10/2006 at 8:18:19 AM. Contact: ###-####. r/i for soffit around mountain
|
ELE06-01982
| Final | 6/11/2006 | 6/12/2006 | 6/12/2006 8:38:29 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/11/2006 at 8:46:44 PM. Contact: ###-####.
|
ELE06-01982
| Electrical Rough-In | 6/12/2006 | 6/12/2006 | 6/12/2006 8:38:15 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/11/2006 at 8:46:44 PM. Contact: ###-####. survey posted label panel bond hot and cold pipe, shall not ID 6 or smaller neutral, derate or remove conductors from conduit
|