ELE07-02124
| Rough-In Permanent Service | 6/12/2007 | 6/12/2007 | 6/12/2007 6:31:04 PM | P | PASS |
|
|
core and shell with service and interior outlets and exterior lights thanks Brad Phone #: ###-#### Internet Inspection Request from: Brad Baker called, told to put in hole plug at service, ric ok, p/s u/g n ok 1 meter only
|
ELE07-01586
| Final | 6/12/2007 | 6/12/2007 | 6/12/2007 3:55:56 PM | P | PASS |
|
|
re-vised final Chris Sirani ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis correction made, ok to final, signed occ card
|
ELE07-01551
| Electrical Rough-In | 6/12/2007 | 6/12/2007 | 6/12/2007 2:27:18 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 6/12/2007 at 8:41:30 AM. Contact: ###-####. - 1st floor corridor and stairwell ok to cover 1st floor corridor and stairwells anop
|
ELE07-02110
| Permanent Service | 6/11/2007 | 6/12/2007 | 6/12/2007 1:35:51 PM | P | PASS |
|
|
Jason ; Phone #: ###-#### Internet Inspection Request from: Darla Downs told owner to add 4 rooms to permit so we can do ri inside ltr, p/s o/h rec ok
|
ELE07-02115
| Permanent Service | 6/12/2007 | 6/12/2007 | 6/12/2007 1:00:33 PM | P | PASS |
|
|
Call Travis if any problems at ###-#### Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa need to final later, check panel, mast height, p/s o/h rec ok
|
ELE07-00886
| Final | 6/12/2007 | 6/12/2007 | 6/12/2007 12:24:50 PM | P | PART |
|
|
Phase 1 only Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to final east part, calling phase 1 , need to see rest, west, later
|
ELE07-02038
| Electrical Rough-In | 6/11/2007 | 6/12/2007 | 6/12/2007 10:20:50 AM | A | PASS |
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to cover u/g, was exposed, had owner drop conduit up by garage to keep 2' depth
|
ELE07-01106
| Final | 6/11/2007 | 6/12/2007 | 6/12/2007 9:22:25 AM | A | PASS |
|
|
warren - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith new subpanel, ok to final
|
ELE07-02113
| Electrical Rough-In | 6/11/2007 | 6/12/2007 | 6/12/2007 9:01:08 AM | A | FAIL |
|
|
We wired 9 new ceiling lighting receptacles and 1 new wall switch in one office utilizing the existing room circuit. Thanks!!! Dan ###-#### Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called, left corr notice, nec 330.30(B) mc cable shall be secured within 12" of box, 300.4(D) mc cable shall be 1 1/4" from edge of framing member
|
ELE07-00557
| Final | 6/12/2007 | 6/12/2007 | 6/12/2007 8:22:50 AM | A | CANC |
|
|
called contr to label meters with addresses, ok to final, both addresses worked on this permit, owner owns both addresses
|
ELE07-02106
| Rough-In Permanent Service | 6/11/2007 | 6/12/2007 | 6/12/2007 8:11:50 AM | A | PASS |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, p/s u/g n ok
|