Inspections for the day of: Tuesday, June 12, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00009 FIR-Aging Inspection6/12/20076/12/20076/19/2007 12:41:14 PM DONE
wip
FIR06-00504 INSP-Sprinkler Rough-in6/11/20076/12/20076/13/2007 11:48:25 AMAPART
4th, 5th and 6th floor overhead rough-in inspection passed, missing two seismic braces on the 6th floor, also noted head spacing to be adjusted due to tenant walls.
FIR06-00948 INSP-Final Inspection6/11/20076/12/20076/12/2007 3:02:12 PMAFAIL
Need to repair the outside bell, provide 911 signage.
BLD06-03194 FIRE-Final Inspection6/12/20076/12/20076/12/2007 2:30:01 PMPPASS
Fire life safety passed field inspection.
MIS07-00125 FIR-Final6/11/20076/12/20076/12/2007 1:36:10 PMAPASS
Fire life safety passed.
MIS07-00124 FIR-Final6/11/20076/12/20076/12/2007 11:42:54 AMAPASS
c/n items are complete, fire life safety inspection passed.
MIS07-00126 FIR-Final6/11/20076/12/20076/12/2007 11:40:29 AMAPASS
Fire life safety inspection passed, contractor to remove tape covering one sprinkler head in the NE corner room.
FIR07-00230 INSP-Sprinkler Rough-in/Hydro6/11/20076/12/20076/12/2007 11:37:10 AMAPART
UG fire supply line hydrostatic test passed inspection.
FIR07-00506 INSP-Sprinkler Rough-in6/11/20076/12/20076/12/2007 10:33:29 AMAPART
TI fire sprinkler modifications are approved for cover at the hard lid ceilings.
FIR07-00233 INSP-Sprinkler Rough-in/Hydro6/11/20076/12/20076/12/2007 10:20:46 AMAFAIL
No hydrostatic test completed due to start pressures well below 200 psi., noted riser manifolds will need to be adjusted to provide access to the flow switches, recommend nailer plates be installed at 1.5" risers to the 2nd floor. C/N items from the previous inspection and tenting for the second floor are acceptable.
FIR07-00507 INSP-Sprinkler Rough-in6/11/20076/12/20076/11/2007 10:17:04 AMACANC
Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley