FIR07-00009
| FIR-Aging Inspection | 6/12/2007 | 6/12/2007 | 6/19/2007 12:41:14 PM | | DONE |
|
|
wip
|
FIR06-00504
| INSP-Sprinkler Rough-in | 6/11/2007 | 6/12/2007 | 6/13/2007 11:48:25 AM | A | PART |
|
|
4th, 5th and 6th floor overhead rough-in inspection passed, missing two seismic braces on the 6th floor, also noted head spacing to be adjusted due to tenant walls.
|
FIR06-00948
| INSP-Final Inspection | 6/11/2007 | 6/12/2007 | 6/12/2007 3:02:12 PM | A | FAIL |
|
|
Need to repair the outside bell, provide 911 signage.
|
BLD06-03194
| FIRE-Final Inspection | 6/12/2007 | 6/12/2007 | 6/12/2007 2:30:01 PM | P | PASS |
|
|
Fire life safety passed field inspection.
|
MIS07-00125
| FIR-Final | 6/11/2007 | 6/12/2007 | 6/12/2007 1:36:10 PM | A | PASS |
|
|
Fire life safety passed.
|
MIS07-00124
| FIR-Final | 6/11/2007 | 6/12/2007 | 6/12/2007 11:42:54 AM | A | PASS |
|
|
c/n items are complete, fire life safety inspection passed.
|
MIS07-00126
| FIR-Final | 6/11/2007 | 6/12/2007 | 6/12/2007 11:40:29 AM | A | PASS |
|
|
Fire life safety inspection passed, contractor to remove tape covering one sprinkler head in the NE corner room.
|
FIR07-00230
| INSP-Sprinkler Rough-in/Hydro | 6/11/2007 | 6/12/2007 | 6/12/2007 11:37:10 AM | A | PART |
|
|
UG fire supply line hydrostatic test passed inspection.
|
FIR07-00506
| INSP-Sprinkler Rough-in | 6/11/2007 | 6/12/2007 | 6/12/2007 10:33:29 AM | A | PART |
|
|
TI fire sprinkler modifications are approved for cover at the hard lid ceilings.
|
FIR07-00233
| INSP-Sprinkler Rough-in/Hydro | 6/11/2007 | 6/12/2007 | 6/12/2007 10:20:46 AM | A | FAIL |
|
|
No hydrostatic test completed due to start pressures well below 200 psi., noted riser manifolds will need to be adjusted to provide access to the flow switches, recommend nailer plates be installed at 1.5" risers to the 2nd floor. C/N items from the previous inspection and tenting for the second floor are acceptable.
|
FIR07-00507
| INSP-Sprinkler Rough-in | 6/11/2007 | 6/12/2007 | 6/11/2007 10:17:04 AM | A | CANC |
|
|
Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|